Measurement lines |
Single-phase 3-wires, Three-phase 3-wires, Single-phase 2-wires (no independent settings for each line) |
Measurement items |
Voltage, Current, Current peak, Active power, Apparent power, Reactive power, Power factor, Phase angle, Frequency, Power integration, Current integration |
Measurement ranges |
Voltage range: 150/ 300/ 600 V AC |
Current range: 500 mA, 1/ 2/ 5/ 10/ 20/ 50 A AC |
Depends on combination of voltage and current range (Power range: 75.000 W to 60.000 kW) |
Frequency range: Auto/ 500 Hz/ 50 kHz (select voltage or current) |
Input resistance (50/60 Hz) |
Voltage: 2 MΩ, Current: 2 mΩ or less (direct input) |
Basic accuracy |
±0.1 % rdg. ±0.1 % f.s. (active power, at 45 to 66 Hz) |
Display refresh rate |
5 times/second |
Frequency characteristics |
10 Hz to 100 kHz |
Integration measurement |
Data update time: 5 times/sec, Measurement range: 0.00000 m to ±999999 MAh/MWh, (integration time up to 10,000 hours) |
Wave peak measurement |
Current 1, 2, 3 (displays maximum absolute value, 3 not available during single phase measurement), Effective input range: Six times the current range, or Max. 90 A peak |
D/A output |
Number of channels: 1 ch, Output items: Voltage, Current, Current peak, Active power, Apparent power, Reactive power, Power factor, Phase angle, Frequency, Integration (each channels value, or sum) |
Analog output |
Voltage, Current, Power simultaneously, DC ±5 V f.s. |
Monitor output |
Voltage, Current simultaneously (waveform output), 1 Vrms f.s. |
Other functions |
Backup, Scaling, Average function |
Interface |
RS-232C, GP-IB standard |
Power requirements |
100 to 240 V AC, 50/60 Hz, 50 VA max. |
Dimensions, mass |
210 mm(8.27 in)W × 100 mm(3.94 in)H × 261 mm(10.28 in)D, 2.5 kg (88.2 oz) |
Supplied accessories |
Instruction Manual × 1, Power cord × 1, Connector for EXT I/O × 1 |
|