- Model: EN3LR-120-12
- UPS Capacity: 3000 VA / 2700 W
- UPS Type: Single-phase, online double-conversion
- Battery Bank: 12 x PSS120 12V 120Ah sealed lead-acid batteries
- Battery Bank Nominal Energy: Approximately 17.28 kWh
- Input Voltage: 230 V ±20%
- Input Frequency: 45–65 Hz
- Output Voltage: 230 VAC ±2%
- Output Frequency in Battery Mode: 50 Hz ±0.1 Hz
- Output Power Factor: 0.9
- Output Waveform: Pure sine wave
- Efficiency: At least 89% in normal mode; up to 97% in ECO mode
- UPS Control Unit: Rack or tower mount, 2 RU
- Display: Interactive LCD showing load, battery, input, output and operating status
- Communications: USB and RS-232 standard; optional SNMP and relay cards
- Battery Type: Sealed, maintenance-free valve-regulated lead-acid
- Battery Bank Enclosure: BB-A16T external free-standing cabinet
- UPS Control Unit Dimensions: 86.5 H x 600 L x 440 W mm
- UPS Control Unit Weight: 26.8 kg
- Complete System Dimensions: Approximately 1200 H x 600 L x 600 W mm, estimated from the external battery cabinet configuration
- Complete System Weight: Approximately 460 kg, estimated from 12 x 120Ah VRLA batteries, cabinet and UPS control unit
- Dimensions (H x L x W): 1200mm x 600mm x 600mm
- Weight: 460 kg
- Online double-conversion power protection for sensitive electrical and electronic equipment
- Extended runtime supplied by an external bank of 12 x 120Ah batteries
- 2700 W active power capacity at 3 kVA
- Interactive LCD monitoring of load, battery, input, output and operating status
- Rack or tower installation for the UPS control unit
- Pure sine-wave output suitable for computers, servers, networking and control equipment
- USB and RS-232 communications included
- Optional SNMP and relay communications for remote monitoring and control
- External free-standing BB-A16T battery enclosure
- Maintenance-free sealed lead-acid battery technology
- Installation and commissioning must be performed by a licensed electrician or suitably qualified UPS technician. The external battery bank contains hazardous voltages and high stored energy. Install, cable, isolate, earth and commission the system in accordance with the manufacturer's instructions, AS/NZS 3000 and applicable UPS safety requirements.
- Server rooms and data centres requiring extended backup runtime
- Telecommunications and networking infrastructure
- Security, surveillance and access-control systems
- Industrial control and automation equipment
- Critical office, medical and commercial electronic equipment
- Sites requiring long-duration backup during extended mains outages
- AS IEC 62040.1: Uninterruptible power systems — General and safety requirements; verify the supplied configuration's certification documentation
- AS IEC 62040.2: Uninterruptible power systems — Electromagnetic compatibility requirements, where applicable to the supplied configuration
- AS/NZS 3000: Electrical installations — Wiring Rules, for permanent electrical installation, isolation, earthing and protection
- Sealed lead-acid batteries are recyclable through approved battery-recycling channels
- Replaceable batteries extend the usable life of the UPS and reduce whole-unit replacement waste
- High-efficiency ECO mode can reduce operating energy consumption under suitable load conditions
- Extended runtime helps prevent equipment shutdowns, data loss and premature replacement of sensitive equipment
- Maintenance-free VRLA battery construction avoids routine electrolyte top-up
Standard PSS Distributors warranty is a 2-year return-to-base warranty from the original purchase date, subject to the published warranty conditions. Battery operation, storage, installation and commissioning requirements apply.
Available through PSS Distributors and authorised Australian electrical, UPS and power-protection distributors; contact the supplier to confirm current availability and lead time.
UPS Sizing Calculator
This calculator follows relevant Australian standards to ensure reliable and compliant performance. It provides an estimated recommendation based on user inputs.
Users must verify specifications before purchasing.