Alternatively Known As: CHINT NXZM 160A Frame ATS, 3-Phase Automatic Transfer Switching Equipment, Mains-Generator Changeover Switch

Technical Specifications
  • Model: NXZM-160H/3A
  • Equipment Class: CB automatic transfer switching equipment
  • Rated Current: 125 A
  • Frame Current: 160 A
  • Number of Poles: 3P
  • Rated Operational Voltage: 400/415 V AC
  • Rated Frequency: 50 Hz
  • Utilisation Category: AC-33B
  • Rated Insulation Voltage: 800 V AC
  • Rated Impulse Withstand Voltage: 8 kV
  • High Breaking Capacity: 50 kA rated short-circuit breaking capacity
  • Rated Short-Circuit Making Capacity: 105 kA
  • Controller: Type A standard controller
  • Control Supply Voltage: 230/240 V AC
  • Control Voltage Range: 85% to 110% of rated voltage
  • Operating Transfer Time: Approximately 3.3 seconds
  • Installation: Integrated or split controller installation
  • Enclosure Protection: IP20
  • Operating Temperature: -5°C to +40°C
  • Maximum Recommended Altitude: 2000 m above sea level
  • Dimensions (H x L x W): 340mm x 307mm x 250mm
  • Weight: 6.5 kg
Key Features
  • Three-pole automatic changeover between normal and alternative power supplies
  • 125A rated current in a 160A frame
  • High-breaking H configuration for increased short-circuit capability
  • Type A standard controller for automatic monitoring and transfer
  • Suitable for mains-generator and grid-grid changeover applications
  • Manual and automatic operating modes
  • Adjustable transfer and return delay settings
  • Built-in electrical and mechanical interlocking
  • Designed for low-voltage emergency power systems
Professional Installation Requirements
  • Installation, commissioning and maintenance must be performed by a licensed electrician or suitably qualified electrical professional. Wiring and integration with mains and generator supplies must comply with AS/NZS 3000, applicable generator installation requirements and the manufacturer's instructions.
Applications
  • Mains-generator automatic changeover systems
  • Commercial and industrial emergency power supplies
  • Standby generator installations
  • Building services and essential-load switchboards
  • Three-phase distribution and backup power systems
Standards & Compliance
  • AS/NZS 3947.6.1:2001 for low-voltage automatic transfer switching equipment, subject to project and regulatory requirements
  • AS/NZS 3000 for electrical installation and wiring requirements
Environmental Benefits
  • Metal components can be separated and recycled at end of service life
  • Automatic transfer operation supports continuity of essential services and can reduce losses associated with prolonged power interruptions
  • Durable switchgear construction can extend service life and reduce replacement waste
  • Product components should be disposed of through appropriate industrial electrical equipment recycling channels
Warranty Information

CHINT's general warranty policy for other low-voltage apparatus is 27 months from the date of manufacture when purchased through authorised sales channels. Contract-specific terms may vary.