SCHNAP Logo

Making Trade Life Easy!
Trade Discount 25%

ATS 3P 200A High Breaking Type A 250A Frame NXZM Chint

BRAND: CABAC
SKU: 297203
$3,434.10 List price: $4,578.80
+ −
Chint NXZM 200A 3P ATS features CB class changeover, Type A standard controller, high breaking capacity and 250A frame. Ideal for mains-generator changeover.

Alternatively Known As: CHINT NXZM 200A ATS, 3-Phase Automatic Changeover Switch, Mains-Generator Transfer Switch, Class CB ATS

Technical Specifications
  • Model: NXZM-250H/3A 200A
  • Equipment Class: CB automatic transfer switching equipment
  • Rated Current: 200A
  • Frame Current: 250A
  • Number of Poles: 3P
  • Rated Operational Voltage: 400/415V AC, 50Hz
  • Rated Insulation Voltage: 800V AC
  • Rated Impulse Withstand Voltage: 8kV
  • Utilisation Category: AC-33B
  • High Breaking Capacity: 50kA rated short-circuit breaking capacity
  • Rated Short-Circuit Making Capacity: 105kA
  • Mechanical Endurance: 2,000 operations
  • Electrical Endurance: 1,500 operations
  • Controller: Type A standard controller
  • Control Supply: 230/240V AC, 50Hz
  • Control Voltage Range: 85% to 110% of rated voltage
  • Typical Operating Transfer Time: 3.3 seconds
  • Installation Configuration: Integrated controller and transfer switch
  • Product Standard: IEC 60947-1 and IEC 60947-6-1
  • Dimensions (H x L x W): 240mm x 216mm x 393mm
  • Weight: 8 kg
Key Features
  • 3-pole automatic transfer between normal and standby supplies
  • Class CB design incorporating mechanically interlocked circuit breakers
  • High H-type breaking capacity for higher fault-current environments
  • 200A rated current within a 250A frame
  • Type A standard controller for automatic and manual transfer operation
  • Suitable for mains-generator and other standby power changeover applications
  • Manual operation and reset capability
  • Designed for AC systems up to 400/415V
  • Durable moulded-case construction for commercial and industrial switchboards
Professional Installation Requirements
  • Installation, wiring, commissioning and testing must be performed by a licensed electrical contractor. The changeover arrangement should be designed and installed in accordance with AS/NZS 3000 and AS/NZS 3010, including correct neutral treatment, source isolation, generator interlocking and prevention of back-feed. Type A controllers do not provide generator-control or fire-fighting feedback functions.
Applications
  • Mains-to-generator automatic changeover
  • Standby power systems
  • Commercial and industrial switchboards
  • Emergency power distribution
  • Data centres, communications facilities and essential services
  • Three-phase load transfer between two compatible AC supplies
Standards & Compliance
  • Applicable product standard: AS/NZS IEC 60947.6.1:2015 for transfer switching equipment
  • Installation context: AS/NZS 3010:2017 for electrical installations incorporating generating sets
  • Installation wiring and switchboard integration should comply with AS/NZS 3000
Environmental Benefits
  • Long service life and high operating endurance can reduce replacement frequency and associated waste
  • Moulded-case switchgear contains recyclable metal components, including copper and steel elements
  • Automatic transfer helps maintain continuity of essential electrical systems and can support efficient use of standby generation
  • Designed for repairable, serviceable switchboard integration rather than disposable single-use applications
Warranty Information

CHINT warranty coverage varies by market and sales channel. CHINT product documentation commonly specifies coverage against manufacturing defects for 12 months from purchase or 18 months from production, whichever occurs first; confirm the applicable terms with the authorised distributor.

Available Now

Available through authorised CHINT distributors in Australia.