ATS 3P 315A High Breaking Type A 400A Frame NXZM Chint
Chint NXZM 315A 3P ATS features CB class changeover, Type A standard controller, high breaking capacity and 400A frame. Ideal for mains-generator changeover.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NXZM 315A ATS, 3-Phase Automatic Changeover Switch, Mains-Generator Transfer Switch, CB-Class ATS
- Series: NXZM
- ATS Type: CB class, circuit-breaker based
- Frame Current: 400A
- Rated Current: 315A
- Number of Poles: 3P
- Controller: Type A standard controller
- Rated Operational Voltage: 400/415V AC
- Frequency: 50Hz
- Utilisation Category: AC-33B
- High Breaking Capacity: 70kA maximum circuit-breaker rating at 400V AC
- Rated Control Voltage: 230/240V AC
- Control Voltage Range: 85% to 110% of rated voltage
- Operating Transfer Time: Approximately 3.5 seconds
- Mechanical Endurance: 4,000 operations
- Electrical Endurance: 1,500 operations
- Installation: Surface or mounting-plate installation
- Connection: Cable or busbar connection
- Operating Temperature: -5°C to +40°C
- Pollution Degree: 3
- Dimensions (H x L x W): 334mm x 540mm x 234mm
- Weight: 18.78 kg
- Automatic transfer between normal and alternative power supplies
- Suitable for mains-generator and grid-grid changeover applications
- CB-class design provides overload and short-circuit protection through integral moulded-case circuit breakers
- High breaking-capacity H frame for installations with higher prospective fault current
- Standard Type A controller with automatic transfer and restoration functions
- Manual operation facility for commissioning, isolation and emergency control
- Can be installed vertically or horizontally
- Suitable for industrial, commercial and critical-load power systems
- Installation, testing and commissioning must be performed by a licensed electrical contractor. The transfer switch must be selected, wired and commissioned in accordance with AS/NZS 3000, AS/NZS 3010, applicable supply authority requirements and the manufacturer's instructions. Particular attention is required for source interlocking, phase sequence, neutral arrangements, generator control and protection coordination.
- Mains-to-generator automatic changeover
- Standby power systems
- Commercial and industrial switchboards
- Critical-load power distribution
- Data centres, facilities and infrastructure requiring alternate-source supply
- Grid-to-grid automatic transfer applications
- Applicable to automatic transfer switching equipment under AS/NZS 60947.6.1
- Installation in generating-set applications should comply with AS/NZS 3010
- Electrical installation and switchboard integration should comply with AS/NZS 3000 and applicable AS/NZS 61439 requirements
- Automatic transfer helps maintain continuity of supply and can reduce downtime-related energy and material losses
- Durable circuit-breaker-based construction and rated switching endurance can extend service life and reduce replacement waste
- Metallic and polymer components may be recoverable through appropriate electrical-equipment recycling streams at end of life
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels, unless a contract specifies different terms. Warranty normally covers defects in materials and workmanship and excludes incorrect installation, misuse, unauthorised modification and non-compliant operation.
Available through authorised CHINT distributors in Australia.