ATS 3P 80A Type A 125A Frame NXZM Chint
Chint NXZM 80A 3P ATS features CB class changeover, Type A standard controller and 125A frame. Ideal for mains-generator changeover.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NXZM-125S/3A 80A ATS, 80A Automatic Changeover Switch, Mains-Generator Transfer Switch
- Product Type: Automatic transfer switching equipment
- Model: NXZM-125S/3A 80A
- Transfer Class: Class CB
- Number of Poles: 3P
- Frame Current: 125A
- Rated Current: 80A
- Controller: Type A standard controller
- Rated Operational Voltage: 400/415V AC, 50Hz
- Rated Insulation Voltage: 800V AC
- Rated Impulse Withstand Voltage: 8kV
- Utilisation Category: AC-33B
- Rated Short-Circuit Making Capacity: 52.5kA
- Rated Short-Circuit Breaking Capacity: 25kA
- Mechanical Endurance: 10,000 operations
- Electrical Endurance: 2,000 operations
- Control Supply: 230/240V AC, 50Hz
- Control Voltage Range: 85% to 110% of rated voltage
- Typical Transfer Time: 2.8 seconds ±10%
- Installation: Integrated or split installation
- Controller Limitation: Type A controller does not provide generator control or fire-fighting feedback functions
- Dimensions (H x L x W): 240mm x 345mm x 180mm
- Weight: 8.5 kg
- Automatic changeover between mains and standby generator supplies
- Circuit-breaker-based Class CB transfer equipment with short-circuit interruption capability
- Three-pole configuration for three-phase systems
- 125A frame with an 80A rated current
- Type A standard controller for straightforward automatic transfer operation
- Manual operating handle for local control and reset
- Suitable for industrial, commercial and building electrical installations
- Designed for 400/415V AC, 50Hz power systems
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, applicable generator installation requirements and the manufacturer's instructions. Generator-connected installations should be assessed against AS/NZS 3010, including neutral, earthing, interlocking and backfeed protection requirements.
- Mains-to-generator automatic changeover
- Standby power systems
- Commercial switchboards
- Industrial electrical installations
- Residential buildings with three-phase backup generation
- Critical-load and emergency power distribution
- Applicable transfer-switch equipment standard: AS/NZS IEC 60947.6.1:2015
- Generator changeover installations should comply with AS/NZS 3010:2017
- Electrical installation and switchboard wiring should comply with AS/NZS 3000:2018
- Metal components can be recovered and recycled at end of product life
- Durable moulded-case construction can reduce replacement frequency and associated waste
- Supports reliable use of standby generation, helping maintain electrical service continuity without installing duplicate distribution equipment
CHINT NXZ automatic transfer switch instructions specify a 36-month warranty from the date of production under normal storage, transport and operating conditions, subject to exclusions for misuse, unauthorised repair, force majeure and other stated conditions.
Available through authorised CHINT distributors in Australia.