Chint NXZM 250A 4P ATS features CB class changeover, Type B intelligent controller, high breaking capacity and 400A frame. Ideal for mains-generator changeover.

Alternatively Known As: CHINT NXZM 400A Frame ATS, 250A 4P Automatic Changeover Switch, CB Class Automatic Transfer Switching Equipment

Technical Specifications
  • Product Type: CB class automatic transfer switching equipment
  • Frame Current: 400 A
  • Rated Current: 250 A
  • Number of Poles: 4P
  • Rated Operational Voltage: 400/415 V AC, 50 Hz
  • Rated Insulation Voltage: AC 1000 V
  • Rated Impulse Withstand Voltage: 12 kV
  • Utilisation Category: AC-33B
  • Rated Short-Circuit Making Capacity: 154 kA
  • Rated Short-Circuit Breaking Capacity: 70 kA
  • Controller: Type B intelligent controller
  • Controller Installation: Integrated or split
  • Rated Control Power Supply: 230/240 V AC, 50 Hz
  • Control Voltage Range: 85% to 110% of rated voltage
  • Operating Transfer Time: 3.5 seconds ±10%
  • Mechanical Endurance: 1500 operations
  • Electrical Endurance: 1500 operations
  • Installation Orientation: Vertical or horizontal
  • Applicable Supply: Three-phase, four-wire dual-supply systems
  • Dimensions (H x L x W): 342mm x 535mm x 234mm
  • Weight: 30 kg
Key Features
  • High breaking capacity H type configuration
  • Four-pole changeover switches the three phases and neutral
  • Type B intelligent controller for automatic monitoring and transfer control
  • CB class construction using mechanically interlocked circuit-breaker mechanisms
  • Suitable for mains-to-generator changeover applications
  • Manual and automatic operating modes
  • Adjustable transfer and return delay functions
  • Generator start control and RS485 communication functions available through the intelligent controller
  • Suitable for industrial, commercial, high-rise and residential power systems
Professional Installation Requirements
  • Installation, commissioning and testing must be performed by a licensed electrical contractor. The mains, generator, neutral switching, protection, earthing and control wiring must be designed and installed in accordance with AS/NZS 3000 and AS/NZS 3010, with the generator isolated from the utility supply to prevent backfeed.
Applications
  • Automatic mains-to-generator changeover
  • Standby power systems
  • Industrial and commercial switchboards
  • High-rise building emergency power systems
  • Residential backup generator installations
  • Critical-load and continuity-of-supply applications
Standards & Compliance
  • AS/NZS 3000 for electrical installations and wiring requirements
  • AS/NZS 3010 for electrical installations incorporating generating sets and automatic changeover equipment
Environmental Benefits
  • Long service life helps reduce replacement frequency and associated electrical equipment waste
  • Copper, aluminium and steel components can be recovered for recycling at end of product life
  • Supports efficient use of standby generation by automatically transferring loads between available power sources
Warranty Information

CHINT warranty policy for other low-voltage apparatus is 27 months from the date of manufacture when purchased through authorised sales channels; contract terms may vary.

Available Now

Available through authorised CHINT distributors in Australia.