ATS 4P 315A High Breaking Type A 400A Frame NXZM Chint
Chint NXZM 315A 4P ATS features CB class changeover, Type A standard controller, high breaking capacity and 400A frame. Ideal for mains-generator changeover.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NXZM 315A ATS, 4-Pole Automatic Changeover Switch, Mains-Generator Transfer Switch
- Product Model: NXZM-400H/4A 315A
- Switching Class: CB automatic transfer switching equipment
- Number of Poles: 4P
- Frame Current: 400A
- Rated Current: 315A
- Rated Operational Voltage: 400/415V AC, 50Hz
- Rated Insulation Voltage: 1000V AC
- Rated Impulse Withstand Voltage: 12kV
- Utilisation Category: AC-33B
- High Breaking Capacity: 70kA rated short-circuit breaking capacity
- Rated Short-Circuit Making Capacity: 154kA
- Controller: Type A standard controller with LED indication
- Control Supply: 230/240V AC, 50Hz
- Control Voltage Range: 85% to 110% of rated voltage
- Transfer Time: 3.3 seconds, plus or minus 10%
- Mechanical Endurance: 4,000 operations
- Electrical Endurance: 1,500 operations
- Installation Mode: Integrated or split installation
- Dimensions (H x L x W): 334mm x 535mm x 234mm
- Weight: 24 kg
- Four-pole automatic transfer switching for three-phase supplies
- CB class construction using circuit-breaker-based switching
- High breaking capacity for demanding mains-generator applications
- 315A rated current within a 400A frame
- Type A standard controller with visual operating indication
- Supports automatic transfer between normal and alternative power sources
- Manual and automatic operating modes with an off position
- Mechanical interlocking helps prevent simultaneous connection of both sources
- Suitable for grid-generator and grid-grid changeover systems
- Installation, commissioning and testing must be performed by a licensed electrical contractor. The installation must be designed and wired in accordance with the manufacturer's instructions, AS/NZS 3000 and, where connected to a generating set, AS/NZS 3010.
- Mains-generator automatic changeover systems
- Commercial and industrial switchboards
- Standby power systems
- Critical power supply installations
- Data centres, telecommunications facilities and infrastructure sites
- Three-phase four-wire distribution systems
- AS/NZS 3000 for electrical installations and changeover arrangements
- AS/NZS 3010 for electrical installations incorporating generating sets
- IEC 60947-1 and IEC 60947-6-1 product standards
- Supports the use of standby generation to maintain essential services and reduce downtime during mains interruptions
- Long mechanical and electrical service life can reduce replacement frequency and associated material waste
- Durable switchgear construction supports extended equipment service life
CHINT low-voltage apparatus is covered for defects in materials and workmanship for 27 months from the date of manufacture when purchased through authorised sales channels, subject to the applicable sales contract and warranty conditions.