Contactor 65A 4P 2NO 2NC 24V DC Coil NC1 Chint
Chint NC1 contactor features 65A rating, 4-pole with 2NO+2NC main contacts and 24V DC coil. Ideal for motor control and DOL starters.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NC1 65A contactor, 4-pole motor contactor, 2NO 2NC contactor, DOL starter contactor
- Model: NC1-6508Z 24V
- Rated Operational Current: 65A at AC-3
- Pole Configuration: 4-pole
- Main Contact Configuration: 2 normally open and 2 normally closed
- Coil Voltage: 24V DC
- Rated Insulation Voltage: 690V AC
- Rated Impulse Withstand Voltage: 8kV
- Utilisation Category: AC-3 and AC-4
- Maximum Motor Rating: 30kW at 380/400V AC-3
- Enclosure Protection: IP10
- DC Coil Power: 22W
- Operating Temperature: -5°C to +40°C
- Mounting: Screw mounting; install with inclination not exceeding ±5°
- Dimensions (H x L x W): 129mm x 127mm x 84mm
- Weight: 1.4 kg
- 65A AC-3 switching capacity for motor-control applications
- Four main poles with integrated 2NO+2NC contact arrangement
- 24V DC coil suitable for control systems using low-voltage DC supplies
- Suitable for remote circuit making and breaking
- Suitable for frequent starting and stopping of AC motors
- Can be combined with compatible thermal overload relays for DOL starters
- Compatible with selected CHINT NC1 accessories
- Mechanical service life up to 6 million operations
- Installation and wiring must be performed by a licensed electrician in accordance with applicable Australian electrical requirements, manufacturer instructions and the design requirements of the controlled motor circuit.
- Motor control panels
- Direct-on-line motor starters
- HVAC and refrigeration control panels
- Industrial automation systems
- Pump and fan control
- Remote switching of AC loads
- Commercial and industrial electrical distribution equipment
- IEC/EN 60947-4-1 product standard for electromechanical contactors and motor starters
- Australian installations should be assessed against AS 60947.4.1 and applicable electrical installation requirements
- Durable electromechanical construction can reduce replacement frequency and product waste
- Metal components such as copper and steel are recyclable at end of service life
- Suitable for integration into motor-control systems designed for efficient load switching
- Low-voltage 24V DC coil operation can reduce control-circuit power requirements compared with higher-voltage coils
CHINT warranty policy for other low-voltage apparatus provides 27 months from the date of manufacture against defects in materials and workmanship when sold through authorised sales channels; contract terms may vary.
Available through authorised CHINT distributors in Australia.