Dual Wiegand Interface Unit RS-485 LAN Flash Upgradeable Tecom
Tecom dual Wiegand interface unit features an RS-485 LAN and remote flash upgrade. Ideal for connecting Wiegand readers to access control systems.
Sign in
Please login to continue to your account.
Alternatively Known As: Tecom S7017A Dual Wiegand Interface, Tecom Dual Reader Interface Module, Wiegand Door Expansion Module
- Model: TS1061
- Alternate Part Number: S7017A
- Power Supply: 11–14 V DC from RS-485 bus or external 12 V DC supply
- Current Consumption: 80 mA
- Wiegand Interfaces: 2
- Inputs: 4
- Relay Outputs: 2
- RS-485 Bus: 1
- Tamper Input: 1
- Operating Temperature: 0–50 °C
- Maximum Cable Length: 1,500 m from ChallengerPlus or Network Access Controller
- Maximum Interfaces: Up to 12 per ChallengerPlus bus; up to 15 or 16 per Network Access Controller bus
- Firmware Upgrade: Remote flash upgrade via CTPlus installer software
- Compatible Systems: Tecom ChallengerPlus and Network Access Controller
- Dimensions (H x L x W): 78mm x 128mm x 21mm
- Weight: 0.225 kg
- Connects two Wiegand card readers to compatible Tecom access control systems
- RS-485 LAN communication supports remote field installation
- Two dedicated relays for door locks, door-open-too-long sounders or other outputs
- Four inputs for door sensors, request-to-exit devices and other monitored inputs
- Tamper connector for enclosure tamper monitoring
- Supports multiple end-of-line resistor values
- Plug-on connectors simplify RS-485 bus and lock-power wiring
- On-board LEDs indicate operating and communications status
- Remote firmware upgrades through CTPlus installer software
- Installation, panel programming and connection to access-control wiring should be performed by a suitably qualified security or access-control technician. Install the board in a suitable enclosure and follow the manufacturer's wiring, power-supply and RS-485 termination requirements.
- Connecting Wiegand card readers to Tecom ChallengerPlus systems
- Connecting Wiegand readers to Tecom Network Access Controller systems
- Two-reader door control applications
- Door lock, request-to-exit and door-position monitoring
- Access-control system expansion in commercial and industrial buildings
- Retrofitting Wiegand readers into compatible Tecom access-control installations
- AS/NZS IEC 60839.11.2:2019 is applicable to the installation and operation of electronic access-control systems and accessory equipment; product-specific certification is not stated in the available datasheet.
- Remote firmware upgrades can extend service life and reduce replacement-related electronic waste
- Compact PCB construction reduces material use compared with a complete enclosed controller
- Electronic components and circuit-board materials may be recoverable through appropriate e-waste recycling at end of life
A 2-year manufacturer warranty is indicated in the Australian product listing title; confirm current warranty terms with the supplying distributor before purchase.
Availability varies because this is an established Tecom product. Check current supply through Tecom/Aritech authorised Australian distributors and specialist access-control suppliers.