MCCB Electronic Energy Metering 4P 40A | 50 kA Breaking Capacity | IP30 Rated | @Each of 1 | by Legrand
MCCB electronic energy metering 4P 40A is designed for low voltage electrical line protection, featuring a 50 kA breaking capacity and integrated earth leakage protection. Ideal for industrial and commercial switchboards, it offers adjustable overload and short circuit settings, ensuring optimal safety and energy monitoring.
Sign in
Please login to continue to your account.
Product Name/Title: MCCB Electronic Energy Metering 4P 40A | 50 kA Breaking Capacity | IP30 Rated | @Each of 1 | by Legrand
Brand: Legrand
SKU: 420482
Alternatively Known As: MCCB with energy metering, Electronic MCCB 40A 4P, DPX3 250 circuit breaker, Earth leakage circuit breaker 4 pole, Legrand DPX3250MIS+RCD
- Rated current: 40 A
- Rated voltage: 220-690 V
- Breaking capacity (Icu) at 400 V, 50 Hz: 50 kA
- Overload release current setting: 16-40 A
- Short-term delayed short-circuit release adjustment: 24-400 A
- Undelayed short-circuit release adjustment: 24-400 A
- Number of poles: 4
- Integrated earth fault protection with adjustable sensitivity (0.03 - 3 A)
- Degree of protection: IP30
- Screw connection for main circuit
- Mounting: DIN rail or plate
- Auxiliary contacts: 1 normally closed, 1 change-over
- With switched-off indicator and integrated under voltage release
- Dimensions (H x L x W): 140mm x 75mm x 90mm
- Weight: 3.5 kg
- Electronic release MCCB with energy metering and earth leakage protection
- Adjustable overload and short circuit protection settings
- Integrated LCD screen for energy, current, voltage, frequency, power, and harmonics monitoring
- Breaking capacity of 50 kA at 400 V
- 4-pole design with screw connection and front side main circuit connection
- IP30 degree of protection
- Suitable for DIN rail or plate mounting in XL³ cabinets
- Equipped with earth leakage module with adjustable sensitivity and tripping times
- Installation must be performed by a qualified electrician to ensure compliance with electrical safety standards and proper integration into switchboards.
- Low voltage electrical line protection
- Switching, control, and isolation in industrial and commercial switchboards
- Energy metering and earth leakage protection in power distribution systems
- Complies with AS/NZS 60947-2 for low voltage switchgear and control gear
- Integrated energy metering helps optimize energy consumption and reduce waste
- Electronic protection reduces risk of electrical faults and fire hazards
Standard Legrand warranty applies, typically 2 years against manufacturing defects.