Internal Battery Pack 30x 12V 9Ah to Suit 30kVA Tower UPS PMU

BRAND: CABAC
SKU: IBPMU30-30-9
$2,296.60 List price: $3,062.10
Free pick up (over 25 kg or over 1 meter)
Contact us for delivery cost
PMU internal battery pack features 30 x 12V 9Ah sealed batteries to suit 30kVA PMU tower UPS. Ideal for factory-fitted UPS backup runtime.

Alternatively Known As: PMU-30 UPS Battery Pack, PMU-T 30kVA Replacement Battery Pack, 30kVA UPS Internal Battery Assembly, Sealed Lead-Acid UPS Battery Bank

Technical Specifications
  • Battery Quantity: 30 batteries
  • Nominal Battery Voltage: 12V per battery
  • Nominal Battery Capacity: 9Ah per battery at 20-hour rate
  • Battery Chemistry: Sealed lead-acid, valve-regulated type
  • Nominal Battery Bank Voltage: Approximately 360V DC when connected in series
  • Nominal Battery Bank Energy: Approximately 3.24kWh
  • Terminal Type: Typically 6.3mm/F2 tab terminals; verify against the installed PMU UPS
  • UPS Compatibility: PMU 30kVA tower UPS
  • Installation Type: Internal, factory-fitted replacement battery pack
  • Battery Standard Reference: IEC 60896-21 and IEC 60896-22 are commonly applicable to stationary valve-regulated lead-acid batteries
  • Pack Dimensions: Estimated from the PMU tower UPS cabinet envelope; confirm before ordering
  • Pack Weight: Approximately 81kg based on 30 batteries at approximately 2.7kg each
  • Dimensions (H x L x W): 868mm x 900mm x 250mm
  • Weight: 81 kg
Key Features
  • Configured specifically for PMU 30kVA tower UPS systems
  • Includes 30 matched 12V 9Ah sealed rechargeable batteries
  • Provides replacement backup energy storage for factory-fitted UPS installations
  • Sealed, non-spillable lead-acid construction suitable for stationary UPS applications
  • Preconfigured battery assembly reduces individual battery selection and compatibility issues
  • Replacement pack supports restoration of designed UPS backup runtime when installed and commissioned correctly
Professional Installation Requirements
  • Installation and commissioning should be performed by a suitably qualified UPS technician or licensed electrician. Isolate mains and DC battery sources before service, follow PMU service procedures, use appropriate battery-handling PPE, and verify polarity, torque, charging voltage and battery string configuration before returning the UPS to service.
Applications
  • Replacement internal battery pack for PMU 30kVA tower UPS systems
  • Factory-fitted UPS backup runtime restoration
  • Critical power protection for servers, telecommunications, medical, industrial and commercial equipment
  • Preventive UPS battery replacement during scheduled maintenance
Standards & Compliance
  • AS 3011.2: Electrical installations — Secondary batteries installed in buildings — Sealed cells
  • AS 62040.1.1: Uninterruptible power systems — General and safety requirements for UPS used in operator access areas
  • AS/NZS 3000: Electrical installations — Wiring Rules, where the battery pack forms part of the connected electrical installation
Environmental Benefits
  • Sealed lead-acid batteries are widely recyclable through approved battery recycling channels, allowing recovery of lead and other materials
  • Replaceable internal batteries can extend the service life of the PMU UPS and reduce premature disposal of the complete UPS
  • Supports continued use of an energy-efficient online UPS system rather than replacing the entire power-protection installation
  • Battery recycling and disposal should be undertaken through an authorised Australian battery recycler; do not place batteries in general waste
Warranty Information

PSS standard warranty information states a 2-year return-to-base warranty for PSS products from the original purchase date, subject to installation, operating and battery-maintenance conditions. Confirm whether the replacement battery pack is covered under the same terms at purchase.

Available Now

Available through PMU/PSS channels and authorised Australian UPS distributors, subject to configuration and replacement-part availability.