Internal Battery Pack 40x 12V 9Ah to Suit 10-20kVA Tower UPS PMU
PMU internal battery pack features 40 x 12V 9Ah sealed batteries to suit 10-20kVA PMU tower UPS. Ideal for factory-fitted UPS backup runtime.
Sign in
Please login to continue to your account.
Alternatively Known As: PMU-T UPS Battery Pack, PMU Tower UPS Replacement Battery Pack, 40-Battery UPS Pack, 12V 9Ah VRLA Battery String
- Battery Quantity: 40 batteries
- Battery Voltage: 12V per battery
- Battery Capacity: 9Ah per battery
- Battery Type: VRLA sealed lead-acid, maintenance-free
- Nominal Battery Bus: Approximately ±240VDC, configured as two 20-battery strings
- Total Nominal Energy: Approximately 4.32kWh
- UPS Compatibility: PMU-T 10kVA and 20kVA tower UPS systems
- Configuration: Factory-fitted internal battery pack
- Dimensions (H x L x W): 868mm x 900mm x 250mm
- Weight: 110 kg
- Designed for PMU 10-20kVA tower UPS systems
- Contains 40 matched 12V 9Ah sealed lead-acid batteries
- Supports UPS backup runtime during mains power interruptions
- VRLA construction is sealed and requires no routine electrolyte topping-up
- Supplied as a complete internal battery pack for compatible UPS equipment
- High-voltage DC battery assembly requiring controlled installation and commissioning
- Installation and replacement should be performed by a licensed electrician or qualified UPS technician. Isolate the UPS, follow the PMU installation procedure, observe high-voltage DC safety requirements and complete commissioning in accordance with applicable Australian electrical and battery-installation standards.
- Replacement battery pack for PMU-T 10kVA tower UPS systems
- Replacement battery pack for PMU-T 20kVA tower UPS systems
- Factory-fitted UPS backup runtime for servers, networking equipment and critical infrastructure
- Industrial, medical, IT and telecommunications power-protection systems
- Relevant UPS safety reference: AS 62040.1, latest edition, for uninterruptible power systems
- Relevant battery installation reference: AS 3011-2019 for secondary batteries installed in buildings
- Relevant stationary battery testing reference: AS 60896:2023 for stationary lead-acid batteries
- Electrical installation work should follow AS/NZS 3000:2018 where applicable
- Lead-acid batteries are recyclable through appropriate battery-recycling programs
- Replacing the battery pack can extend the service life of the existing UPS and reduce equipment waste
- Sealed VRLA construction reduces the risk of electrolyte spills during normal handling
- Supports continued use of UPS equipment, helping protect critical electrical and electronic assets from premature replacement
No PMU-specific public warranty term was located. Confirm the applicable battery and labour warranty with the authorised PMU distributor before purchase; warranty coverage may depend on qualified installation, commissioning, operating temperature and UPS maintenance records.
Available through PMU and authorised Australian distributors, subject to distributor lead times and compatibility confirmation.