Manual Motor Starter 0.1-0.16A 25A Frame NS2 Chint
Chint NS2 manual motor starter features 0.1-0.16A thermal overload, magnetic short-circuit trip, and rotary control. Ideal for DOL motor starting.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NS2-25X Motor Protection Circuit Breaker, Manual Motor Protector, Motor Circuit Breaker
- Model: NS2-25X
- Poles: 3P
- Frame Size: 25 A
- Adjustable Current Range: 0.1-0.16 A
- Rated Operational Voltage: Up to 690 V AC
- Rated Frequency: 50/60 Hz
- Utilisation Category: AC-3
- Thermal Trip Class: 10A
- Instantaneous Magnetic Trip: 1.5 A
- Short-Circuit Breaking Capacity: Up to 100 kA at 400 V with specified backup protection
- Mounting: DIN rail or panel mounting
- Terminal Type: Screw terminals
- Conductor Size: 1-6 mm² copper
- Ingress Protection: IP20
- Dimensions (H x L x W): 91.3mm x 80.5mm x 44.5mm
- Weight: 0.3 kg
- Adjustable thermal overload protection for small three-phase motors
- Magnetic short-circuit protection
- Phase-failure protection
- Rotary manual ON/OFF control with trip indication
- Suitable for direct-on-line motor starting and stopping
- Compact 2.5-module DIN-rail format
- Optional auxiliary contacts, shunt release, undervoltage release and weatherproof enclosure available
- Installation, adjustment and testing should be performed by a licensed electrician or suitably qualified technician. Isolate the supply before installation and size the motor protection setting to the motor nameplate current. Verify Australian approval and RCM requirements before use.
- Direct-on-line starting of small three-phase motors
- Pumps, fans and compact compressors
- Conveyors, mixers and machine tools
- Industrial control panels and automation equipment
- Motor overload, phase-failure and short-circuit protection
- AS/NZS IEC 60947.2 is the relevant Australian/New Zealand standard series for low-voltage circuit breakers
- AS/NZS IEC 60947.4.1 is the relevant Australian/New Zealand standard series for contactors and motor starters
- CHINT documentation specifies IEC/EN 60947.2 and IEC/EN 60947.4.1; confirm local RCM and installation compliance before Australian use
- RoHS-related material restrictions are declared for the NS2 product series
- Reusable protective switching equipment can extend motor and system service life and reduce premature component replacement
- Compact DIN-rail construction minimises material use and panel space
CHINT warranty policy generally provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable policy conditions.
Available through authorised CHINT distributors in Australia.