Manual Motor Starter 1-1.6A 32A Frame NS2-32H Chint
Chint NS2 manual motor starter features 1-1.6A thermal overload, magnetic short-circuit trip, and rotary control. Ideal for DOL motor starting.
Sign in
Please login to continue to your account.
Alternatively Known As: Motor Protection Circuit Breaker, Manual Motor Protective Starter, MPCB, DOL Motor Protector
- Model: NS2-32H
- Number of Poles: 3
- Rated Current: 1.6 A
- Adjustable Thermal Overload Range: 1–1.6 A
- Instantaneous Magnetic Trip: 22.5 A
- Rated Operational Voltage: AC 230/240 V, 400/415 V, 440 V, 500 V or 690 V
- Rated Frequency: 50/60 Hz
- Rated Ultimate Short-Circuit Breaking Capacity: 100 kA at 400/415 V
- Motor Power at 400 V: 0.37 kW
- Motor Power at 440 V: 0.55 kW
- Motor Power at 500 V: 0.75 kW
- Motor Power at 690 V: 1.1 kW
- Ingress Protection: IP20
- Pollution Degree: 3
- Terminal Conductor Size: 1–6 mm²
- Dimensions (H x L x W): 91.3mm x 99.1mm x 44.5mm
- Weight: 0.3 kg
- Adjustable thermal overload protection for small three-phase motors
- Magnetic short-circuit protection integrated into the device
- Manual rotary start, stop and reset control
- Three-pole motor switching and protection
- Suitable for direct-on-line motor starter arrangements when paired with the appropriate contactor or installation equipment
- Compact NS2-32H frame construction
- Designed for industrial control, HVAC, pumping and machinery applications
- Installation and electrical connection should be performed by a licensed electrician in accordance with the manufacturer's instructions, AS/NZS 3000 and applicable local requirements. Select and coordinate upstream short-circuit protection and any DOL contactor or enclosure for the installation.
- Direct-on-line motor starter assemblies
- Small three-phase HVAC and refrigeration motors
- Pumps and circulating equipment
- Machine tools and industrial machinery
- Fans, blowers and other motor-driven equipment
- IEC/EN 60947-2 requirements are specified for the motor-protection circuit-breaker function
- IEC/EN 60947-4-1 requirements are specified for motor-starter applications; the applicable Australian/New Zealand adoption is AS/NZS IEC 60947.4.1:2015
- Electrical installation work should comply with AS/NZS 3000
- Integrated overload and short-circuit protection can help prevent premature motor failure and reduce replacement waste
- Compact integrated construction reduces the number of separate protective components required
- Long service life supports reduced maintenance and equipment waste when correctly installed and coordinated
CHINT's general policy states 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels. Regional, contractual and Australian consumer-law terms may differ.
Available through authorised CHINT distributors in Australia.