- Model: NS2-25-18
- Frame Rating: 25 A
- Rated Operating Current: 18 A
- Thermal Overload Adjustment: 13-18 A
- Poles: 3P
- Rated Operating Voltage: Up to 690 V AC
- Frequency: 50/60 Hz
- Utilisation Category: AC-3
- Short-Circuit Breaking Capacity: 15 kA at 400/415 V AC
- Instantaneous Magnetic Trip Setting: 223 A
- Motor Rating at 230/240 V AC: 4 kW
- Motor Rating at 400/415 V AC: 7.5 kW
- Ingress Protection: IP20
- Mounting: 35 mm DIN rail
- Terminal Capacity: 1-6 mm²
- Conformity Designation: IEC/EN 60947-2 and IEC 60947-4-1
- Dimensions (H x L x W): 91.3mm x 66mm x 44.5mm
- Weight: 0.31 kg
- Adjustable thermal overload protection from 13 to 18 A
- Magnetic short-circuit protection with instantaneous trip
- Manual rotary start and stop control
- Three-pole protection for three-phase motors
- Suitable for direct-on-line motor starting applications
- Integrated motor overload, short-circuit and phase-failure protection
- Compatible with optional auxiliary, shunt-trip and undervoltage-release accessories
- Compact 25 A frame for DIN-rail mounting
- Installation, wiring and commissioning should be performed by a licensed electrician in accordance with the manufacturer's instructions, AS/NZS 3000 and applicable motor-control requirements. Confirm short-circuit coordination and motor settings before energising.
- Direct-on-line starting of three-phase motors
- Motor protection in HVAC and refrigeration equipment
- Pumps, fans and compressors
- Workshop machinery and small industrial motors
- Control panels and motor distribution boards
- Applicable Australian product standards include AS 60947.2 for low-voltage circuit-breakers and AS 60947.4.1 for contactors and motor-starters.
- Electrical installation should comply with AS/NZS 3000 Wiring Rules.
- The product documentation identifies compliance with IEC/EN 60947-2 and IEC 60947-4-1; verify Australian certification and RCM requirements for the intended installation.
- RoHS compliance helps restrict the use of specified hazardous substances.
- Integrated overload and short-circuit protection can reduce the need for separate protective components in a motor circuit.
- Durable reusable construction can reduce replacement frequency and electrical equipment waste.
CHINT's general warranty policy specifies 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to applicable contract terms and exclusions.
Available through authorised CHINT distributors in Australia.