Manual Motor Starter 24-32A 32A Frame NS2 Chint
Chint NS2 manual motor starter features 24-32A thermal overload, magnetic short-circuit trip, and rotary control. Ideal for DOL motor starting.
Sign in
Please login to continue to your account.
Alternatively Known As: Motor Protection Circuit Breaker, Manual Motor Protector, Motor Circuit Breaker, Guardamotor
- Frame Rating: 32A
- Thermal Overload Setting: Adjustable from 24-32A
- Poles: 3-pole
- Rated Insulation Voltage: 690V
- Rated Operating Voltage: AC 230/240V, 400/415V, 440V, 500V or 690V
- Rated Frequency: 50/60Hz
- Utilisation Category: AC-3
- Trip Class: 10A
- Instantaneous Magnetic Trip Setting: 416A
- Short-Circuit Breaking Capacity: 10kA at 400/415V; 5kA at 690V
- Terminal Conductor Size: 1-6mm²
- Ingress Protection: IP20
- Mounting: Suitable for DIN rail installation
- Dimensions (H x L x W): 91.3mm x 66mm x 44.5mm
- Weight: 0.3 kg
- Adjustable thermal overload protection for 24-32A motor current
- Instantaneous magnetic protection against short circuits
- Phase-failure protection for three-phase motors
- Rotary manual start, stop and isolation control
- Suitable for direct-on-line motor starting applications
- Compact 32A frame for motor control panels and switchboards
- Compatible with optional auxiliary, alarm, shunt-trip and undervoltage accessories
- Installation, adjustment and commissioning should be performed by a licensed electrician in accordance with the manufacturer's instructions and AS/NZS 3000. Confirm motor full-load current, prospective fault current, coordination and enclosure requirements before installation.
- Direct-on-line starting of three-phase AC motors
- Motor overload and short-circuit protection
- Industrial control panels and switchboards
- Fans, pumps, compressors and small machinery motors
- Manual motor isolation and local motor control
- Applicable product standard: AS/NZS IEC 60947.4.1 for contactors and motor-starters
- Applicable product standard: AS/NZS 60947.2 for low-voltage circuit-breakers
- Electrical installation should comply with AS/NZS 3000
- Motor overload and phase-failure protection can help prevent premature motor damage and replacement waste
- Durable low-voltage switchgear construction supports extended service life
- Replaceable accessories and serviceable panel integration can reduce whole-unit replacement requirements
CHINT's general policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to applicable contract and local warranty terms.
Available through authorised CHINT distributors in Australia.