Technical Specifications
  • Model: NS2-80/AU11 30–40A
  • Frame Rating: 80A
  • Rated Operational Current: 40A
  • Overload Adjustment Range: 30–40A
  • Number of Poles: 3
  • Auxiliary Contact: 1NO+1NC, side-mounted
  • Rated Insulation Voltage Ui: 690V
  • Rated Operational Voltage Ue: 230–690V AC
  • Rated Frequency: 50/60Hz
  • Utilisation Category: AC-3
  • Trip Class: 10A
  • Instantaneous Magnetic Trip Setting: 560A
  • Short-Circuit Breaking Capacity Icu: 50kA at 400V AC
  • Ingress Protection: IP20
  • Terminal Conductor Size: 2.5–25mm²
  • Ambient Operating Temperature: -25°C to +40°C
  • Motor Rating: Up to 18.5kW at 400V AC
  • Dimensions (H x L x W): 118.4mm x 119.5mm x 63.6mm
  • Weight: 1.52 kg
Key Features
  • Adjustable thermal overload protection from 30A to 40A
  • Magnetic short-circuit protection
  • Rotary ON/OFF control
  • Integrated 1NO+1NC auxiliary contact for status indication or control circuits
  • Three-pole protection for three-phase AC motors
  • Suitable for direct-on-line motor starting applications
  • High interrupting capacity for motor protection applications
  • Compact 80A frame design
Professional Installation Requirements
  • Installation, adjustment and commissioning should be performed by a licensed electrician in accordance with AS/NZS 3000 and the motor manufacturer's requirements. Select and coordinate upstream short-circuit protection for the installation.
Applications
  • Direct-on-line starting and protection of three-phase AC motors
  • HVAC and refrigeration plant motor circuits
  • Fans, pumps and compressors
  • Industrial machinery and material-handling equipment
  • Motor control panels and switchboards
Standards & Compliance
  • AS/NZS IEC 60947.4.1:2015 — applicable standard for low-voltage contactors and electromechanical motor-starters
  • AS/NZS 3000 — applicable installation requirements for low-voltage electrical equipment
Environmental Benefits
  • Motor overload and short-circuit protection can help prevent premature motor failure and reduce replacement waste
  • Extended service life of protected motors and switchgear can reduce maintenance-related material consumption
  • Metallic electrical components can generally be recovered through established recycling streams at end of life
  • Supports efficient motor system operation by helping maintain correctly protected and adjusted motor circuits
Warranty Information

CHINT's general warranty policy lists 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels. Regional terms, contract conditions and Australian consumer guarantees may apply.

Available Now

Available through authorised CHINT distributors in Australia.