Manual Motor Starter 4-6.3A 25A Frame NS2 Chint
Chint NS2 manual motor starter features 4-6.3A thermal overload, magnetic short-circuit trip, and rotary control. Ideal for DOL motor starting.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT Motor Protection Circuit Breaker, CHINT Manual Motor Protector, NS2-25 4-6.3A Motor Starter
- Frame Rating: 25 A
- Setting Current Range: 4-6.3 A
- Rated Operating Voltage: AC 230/240, 400/415, 440, 500 and 690 V
- Rated Frequency: 50/60 Hz
- Motor Rating at 400/415 V: 2.2 kW, AC-3
- Instantaneous Magnetic Trip Current: Approximately 78 A
- Trip Class: 10A
- Rated Insulation Voltage: 690 V
- Rated Impulse Withstand Voltage: 8 kV
- Protection Rating: IP20
- Terminal Conductor Size: 1-6 mm²
- Terminal Screw: M4
- Terminal Tightening Torque: 1.7 Nm
- Mounting: Suitable for standard electrical control-panel installation
- Dimensions (H x L x W): 91.3mm x 66mm x 44.5mm
- Weight: 0.313 kg
- Adjustable thermal overload protection from 4 to 6.3 A
- Magnetic short-circuit protection for rapid fault disconnection
- Manual motor starting and stopping control
- Phase-failure protection for three-phase motors
- Suitable for direct-on-line motor starting applications
- AC-3 motor control up to 2.2 kW at 400/415 V
- Optional auxiliary, undervoltage, shunt-trip and fault-signal accessories available
- Compact 25 A frame design
- Installation, wiring and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and applicable local electrical requirements. Confirm short-circuit coordination, motor full-load current and required upstream protection before installation.
- Direct-on-line starting of small three-phase motors
- Motor overload and short-circuit protection
- HVAC fans, pumps and compressors
- Workshop machinery and light industrial motor control
- Electrical control panels and machine automation systems
- Applicable product standard: AS/NZS IEC 60947.4.1:2015 for low-voltage contactors and motor-starters
- Circuit-breaker protection requirements may also relate to AS/NZS IEC 60947.2:2015
- The manufacturer documentation references IEC/EN 60947-2 and IEC 60947-4-1; verify product-specific Australian approval and RCM requirements before installation
- Overload and phase-failure protection can help prevent premature motor replacement and reduce equipment waste
- Reusable protective switchgear supports long service life compared with disposable protective components
- Helps protect motor systems from overheating and avoidable electrical fault damage
CHINT's general policy specifies a 27-month warranty from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable sales contract and warranty conditions.
Available through authorised CHINT distributors in Australia.