Manual Motor Starter 6-10A 32A Frame NS2-32H Chint
Chint NS2 manual motor starter features 6-10A thermal overload, magnetic short-circuit trip, and rotary control. Ideal for DOL motor starting.
Sign in
Please login to continue to your account.
Alternatively Known As: Motor Protection Circuit Breaker, Manual Motor Protector, Motor Starter Overload Protector, MPCB
- Model: NS2-32H 6–10A
- Frame Size: 32A
- Number of Poles: 3P
- Adjustable Current Range: 6–10A
- Rated Insulation Voltage: 690V AC
- Rated Frequency: 50/60Hz
- Motor Rating at 400V AC: 4kW
- Trip Class: 10A
- Short-Circuit Protection: Magnetic instantaneous trip
- Instantaneous Trip Setting: 138A
- Control Type: Direct rotary handle
- Mounting: DIN rail mounting
- Terminal Type: Screw terminals
- Conductor Capacity: 1–6mm²
- Ingress Protection: IP20
- Application Category: AC-3, Class A
- Compatible Accessories: Auxiliary contacts, undervoltage releases, shunt releases and mounting enclosures
- Dimensions (H x L x W): 91.3mm x 99.1mm x 44.5mm
- Weight: 0.4 kg
- Adjustable thermal overload protection from 6 to 10A
- Magnetic protection against motor short circuits
- Direct rotary on/off control
- Three-pole motor protection for three-phase applications
- Suitable for direct-on-line motor starting when correctly selected with a contactor
- DIN rail mounting for switchboards and control panels
- High short-circuit withstand capability
- Accessory options available for undervoltage release, shunt trip and auxiliary signalling
- Installation and electrical connection should be performed by a licensed electrician in accordance with the manufacturer's instructions, AS/NZS 3000 and applicable motor-starter requirements. Confirm coordination with the contactor, upstream short-circuit protection and motor nameplate current before commissioning.
- Direct-on-line starting of three-phase AC motors
- Motor overload and short-circuit protection
- HVAC and refrigeration plant control panels
- Pumps, fans and compressors
- Industrial machinery and light commercial motor control assemblies
- Relevant Australian/New Zealand product standard: AS/NZS IEC 60947.4.1:2015 for contactors and motor-starters
- Installation should comply with AS/NZS 3000 electrical installation requirements
- CHINT product documentation references IEC/EN 60947-2 and IEC 60947-4-1; verify local RCM and project compliance requirements before use
- Overload protection can help prevent premature motor failure and reduce replacement waste
- Supports reliable operation of correctly sized motors and associated HVAC/R equipment
- Long service life of the protective device can reduce maintenance and disposal frequency
- Electrical components should be recycled through appropriate e-waste or electrical equipment recycling channels at end of life
CHINT's published general policy states 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels, subject to the applicable contract and warranty conditions.
Available through authorised CHINT distributors in Australia.