Manual Motor Starter 9-14A 25A Frame NS2 Chint
Chint NS2 manual motor starter features 9-14A thermal overload, magnetic short-circuit trip, and rotary control. Ideal for DOL motor starting.
Sign in
Please login to continue to your account.
Alternatively Known As: Motor Protection Circuit Breaker, Manual Motor Protector, DOL Motor Starter
- Model: NS2-25-14
- Poles: 3P
- Frame Rated Current: 25A
- Thermal Overload Adjustment: 9–14A
- Rated Operating Voltage: Up to 690V AC
- Rated Insulation Voltage: 690V
- Rated Impulse Withstand Voltage: 8kV
- Frequency: 50/60Hz
- Trip Class: 10A
- Magnetic Trip Setting: 170A
- Utilisation Category: AC-3
- Motor Rating at 230/240V: 3kW
- Motor Rating at 400/415V: 5.5kW
- Motor Rating at 440/500V: 7.5kW
- Motor Rating at 690V: 9kW
- Short-Circuit Breaking Capacity: 15kA
- Terminal Conductor Size: 1–6mm²
- Terminal Screw Size: M4
- Terminal Tightening Torque: 1.7N·m
- Mounting: 35mm DIN rail or screw fixing
- Ingress Protection: IP20
- Control: Rotary manual ON/OFF control
- Dimensions (H x L x W): 91.3mm x 66mm x 44.5mm
- Weight: 0.31 kg
- Adjustable thermal overload protection for motors rated from 9A to 14A
- Magnetic instantaneous trip for short-circuit protection
- Three-pole switching for three-phase motor circuits
- Suitable for direct-on-line motor starting applications
- AC-3 motor control performance up to 690V AC
- Compact 25A frame design
- Compatible with selected CHINT auxiliary, shunt-trip and undervoltage accessories
- Installation and connection should be performed by a licensed electrician in accordance with the manufacturer's instructions, AS/NZS 3000 and applicable electrical safety requirements. Confirm motor full-load current and fault levels before selection.
- Direct-on-line starting of three-phase motors
- Motor overload and short-circuit protection
- HVAC and refrigeration plant motor circuits
- Pumps, fans and small industrial machinery
- Control panels and motor starter assemblies
- Manufacturer specifies IEC/EN 60947-2 and IEC 60947-4-1; verify the applicable AS/NZS adoption, RCM requirements and local approval requirements before installation.
- Electrical installation should comply with AS/NZS 3000 Wiring Rules.
- Helps protect motors from overload and short-circuit damage, potentially extending equipment service life and reducing replacement waste
- A durable reusable protective device can reduce the need for disposable protective components
- The compact design reduces material use compared with larger motor protection assemblies
CHINT's general policy provides 27 months from the date of manufacture for other low-voltage apparatus purchased through authorised sales channels, subject to contract terms and applicable Australian consumer guarantees.
Available through authorised CHINT distributors in Australia.