MCCB 2P 100A 150kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 100A 2P MCCB features 150kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-125R thermal-magnetic moulded case circuit breaker, 2-pole MCCB, high-breaking-capacity circuit breaker
- Product Designation: NM8N-125R TM 2P 100A
- Breaker Type: Moulded case circuit breaker
- Rated Current: 100 A
- Frame Size: 125 A
- Number of Poles: 2P
- Trip Unit: Adjustable thermal-magnetic
- Overload Adjustment Range: 70–100 A
- Rated Insulation Voltage Ui: 1,000 V AC
- Rated Operational Voltage Ue: Up to 690 V AC, 50/60 Hz
- Ultimate Short-Circuit Breaking Capacity Icu: 150 kA at 380–415 V AC
- Service Short-Circuit Breaking Capacity Ics: 150 kA at 380–415 V AC
- Breaking Capacity at 440 V AC: 100 kA
- Breaking Capacity at 500 V AC: 50 kA
- Breaking Capacity at 660–690 V AC: 10 kA
- Utilisation Category: A
- Ingress Protection: IP40
- Pollution Degree: 3
- Mechanical Life: Up to 25,000 operating cycles
- Electrical Life: Up to 10,000 operating cycles at 415 V AC
- Installation Orientation: Vertical or horizontal mounting, with top or bottom line entry options
- Dimensions (H x L x W): 140mm x 78.5mm x 62mm
- Weight: 0.83 kg
- High 150 kA short-circuit breaking capacity at 380–415 V AC
- Thermal-magnetic protection for overload and short-circuit conditions
- Adjustable thermal overload setting from 70 A to 100 A
- Compact 125 A frame suitable for 2-pole installations
- Suitable for switchboard mains, sub-mains and distribution protection
- Suitable for isolation when installed in accordance with the applicable requirements
- Optional auxiliary and operational accessories are available for the NM8N range
- Installation, adjustment and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and applicable switchboard requirements. Verify prospective fault current, discrimination, cable capacity, terminal torque and local certification requirements before energisation.
- Switchboard mains protection
- Sub-main protection
- Commercial and industrial distribution boards
- Low-voltage AC distribution systems
- Protection of feeders, cables and connected equipment against overload and short circuit
- Applicable product standard: AS/NZS IEC 60947.2:2015 for low-voltage circuit-breakers
- Installation should comply with AS/NZS 3000 Electrical installations
- Confirm Australian certification and RCM requirements for the specific supply configuration before installation
- Overload and short-circuit protection can help prevent damage to connected electrical equipment and reduce premature replacement waste
- Long mechanical and electrical service life supports extended product use
- Metal and polymer components can be separated for appropriate electrical-equipment recycling at end of life
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus, when purchased through authorised sales channels, subject to the applicable sales contract and warranty conditions.
Available through authorised CHINT distributors in Australia.