MCCB 2P 32A 150kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 32A 2P MCCB features 150kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, MCCB, 2-Pole Circuit Breaker, Thermal-Magnetic Circuit Breaker
- Rated Current: 32 A
- Frame Size: 125 A
- Poles: 2P
- Trip Unit: Thermal-magnetic
- Breaking Capacity: 150 kA at 380–415 V AC
- Rated Insulation Voltage: 1,000 V AC
- Rated Frequency: 50/60 Hz
- Overload Trip Adjustment: 22.4–32 A
- Ingress Protection: IP40
- Operating Temperature: -40°C to +70°C
- Mechanical Life: Up to 15,000 cycles
- Electrical Life: Up to 8,000 cycles
- Utilisation Category: Category A
- Installation: Fixed mounting with top or bottom line entry
- Dimensions (H x L x W): 140mm x 78.5mm x 62mm
- Weight: 0.81 kg
- High 150kA short-circuit breaking capacity at 380–415V AC
- Thermal-magnetic protection for overload and short-circuit faults
- Compact 125A frame suitable for switchboards and distribution boards
- Two-pole construction for single-phase and two-conductor circuit protection
- Suitable for isolation and vertical or horizontal installation
- Optional auxiliary, alarm, shunt-release and undervoltage accessories available
- Installation, selection, testing and commissioning should be performed by a licensed electrician in accordance with applicable Australian wiring rules, manufacturer instructions and switchboard requirements. Verify fault levels, discrimination, cable capacity and required RCM compliance before installation.
- Switchboard mains protection
- Sub-mains protection
- Commercial and industrial distribution boards
- Low-voltage AC power distribution
- Protection of feeders and branch circuits with high prospective fault levels
- AS/NZS 60947.2: Applicable standard for low-voltage circuit-breakers and MCCBs
- AS/NZS 3820: Essential safety requirements for relevant electrical equipment
- AS/NZS 3000: Applicable wiring and installation requirements
- Durable moulded-case construction can extend service life and reduce replacement waste
- Metal and thermoplastic components can be separated and directed to appropriate recycling streams at end of life
- High fault-clearing capability helps limit damage to connected equipment and reduce replacement requirements
- CHINT NM8N series documentation includes a RoHS declaration for restricted substances
CHINT warranty policy for other low-voltage apparatus provides 27 months from the date of manufacture against defects in materials and workmanship when supplied through authorised sales channels; contract or local distributor terms may vary.
Available through authorised CHINT distributors in Australia.