MCCB 2P 50A 150kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 50A 2P MCCB features 150kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N 2-pole moulded case circuit breaker, 50A 150kA MCCB, thermal-magnetic circuit breaker
- Series: NM8N
- Frame Size: 125A
- Rated Current: 50A
- Number of Poles: 2P
- Release Type: Thermal-magnetic
- Breaking Capacity Code: R
- Ultimate Breaking Capacity: 150kA
- Rated Voltage: Up to 690V AC
- Rated Frequency: 50/60Hz
- Ingress Protection: IP40
- Mechanical Endurance: 15,000 operations
- Electrical Endurance: 8,000 operations
- Installation: Front connection; vertical or horizontal mounting with top or bottom line entry
- Dimensions (H x L x W): 140mm x 78.5mm x 62mm
- Weight: 0.87 kg
- Two-pole protection for single-phase and two-conductor distribution circuits
- Thermal-magnetic trip unit for overload and short-circuit protection
- 150kA ultimate short-circuit breaking capacity
- 125A frame with 50A rated current
- Suitable for switchboard mains, sub-mains and commercial or industrial distribution
- Can be installed with line entry from the top or bottom
- Designed for use in ambient temperatures from approximately -40°C to +70°C
- Installation, selection and commissioning should be performed by a licensed electrician in accordance with the manufacturer's instructions, AS/NZS 3000 and applicable switchboard requirements. Verify fault levels, discrimination, conductor sizing and enclosure compatibility before installation.
- Switchboard mains protection
- Sub-mains protection
- Commercial electrical distribution boards
- Industrial low-voltage power distribution
- Protection of cables and electrical equipment against overload and short circuit
- Applicable circuit-breaker product standard: AS/NZS IEC 60947.2:2015
- Installation and coordination requirements should follow AS/NZS 3000:2018
- Durable moulded-case construction supports extended service life and reduces replacement waste
- Metal and thermoplastic components can be separated for recycling at end of service life
- Provides overcurrent protection that can help prevent damage to downstream electrical equipment and associated material waste
CHINT warranty policy covers other low-voltage apparatus, including MCCBs, for 27 months from the date of manufacture when purchased through authorised sales channels. Contractual terms may vary.
Available through authorised CHINT distributors in Australia.