MCCB 2P 63A 150kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 63A 2P MCCB features 150kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, 2-Pole MCCB, Thermal-Magnetic Circuit Breaker, NM8N 125 Frame MCCB
- Rated Current: 63 A
- Number of Poles: 2P
- Frame Size: 125 A
- Trip Unit: Thermal-magnetic, adjustable thermal protection
- Breaking Capacity: 150 kA at 380/415 V AC
- Rated Insulation Voltage: 1000 V AC
- Rated Impulse Withstand Voltage: 8 kV
- Rated Frequency: 50/60 Hz
- Utilisation Category: Category A
- Mounting: Fixed or DIN rail mounting
- Connection: Front or rear connection
- Mechanical Life: Up to 25,000 operating cycles
- Electrical Life: Up to 10,000 operating cycles at 415 V AC
- Manufacturer Standard: IEC/EN 60947-2
- Dimensions (H x L x W): 140mm x 78.5mm x 62mm
- Weight: 0.83 kg
- High 150kA ultimate short-circuit breaking capacity
- Thermal-magnetic protection for overload and short-circuit faults
- Two-pole construction for single-phase mains and sub-mains applications
- 125A frame accommodates a 63A rated trip unit
- Suitable for fixed or DIN rail mounting configurations
- Supports front or rear connection arrangements
- Suitable for isolation when installed in accordance with the applicable requirements
- Installation, testing and commissioning should be performed by a licensed electrician in accordance with AS/NZS 3000, manufacturer instructions and applicable switchboard requirements.
- Switchboard mains protection
- Sub-mains protection
- Commercial and industrial distribution boards
- High fault-level low-voltage distribution systems
- Single-phase power distribution circuits
- AS/NZS 60947.2: Applicable Australian/New Zealand standard for low-voltage circuit-breakers; verify local certification and RCM requirements before installation.
- Metal and thermoplastic components can be recovered through appropriate electrical equipment recycling streams
- Long mechanical and electrical service life can reduce replacement frequency and associated material waste
- Provides reliable fault protection that can help limit damage to downstream electrical equipment
CHINT warranty policy for other low-voltage apparatus provides coverage against defects in materials and workmanship for 27 months from the date of manufacture when supplied through authorised sales channels; contract terms may vary.
Available through authorised CHINT distributors in Australia.