MCCB 2P 80A 50kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 80A 2P MCCB features 50kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-125 MCCB, 2P moulded case circuit breaker, thermal-magnetic circuit breaker
- Rated Current: 80A
- Frame Size: 125A
- Number of Poles: 2P
- Trip Unit: Thermal-magnetic
- Rated Short-Circuit Breaking Capacity: 50kA at 380/400/415V AC
- Rated Operational Voltage: Up to 690V AC, 50/60Hz
- Rated Insulation Voltage: 1000V AC
- Rated Impulse Withstand Voltage: 8kV
- Utilisation Category: A
- Isolation Capability: Suitable for isolation
- Product Standard: IEC/EN 60947-2
- Mechanical Life: Up to 25,000 operations
- Electrical Life: Up to 10,000 operations at 415V AC and rated current
- Dimensions (H x L x W): 140mm x 78.5mm x 62mm
- Weight: 0.83 kg
- 2-pole protection for single-phase or two-line distribution circuits
- Thermal-magnetic trip protection for overload and short-circuit faults
- 50kA breaking capacity at 380/400/415V AC
- 125A frame accommodates the 80A thermal-magnetic rating
- Suitable for switchboard mains, sub-mains and distribution protection
- Compact moulded-case construction with zero arcing distance
- Accessory options are available for compatible auxiliary and alarm contacts
- Installation, selection and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the switchboard manufacturer's requirements and applicable protection-coordination requirements.
- Switchboard mains protection
- Sub-mains protection
- Commercial and industrial distribution boards
- Overcurrent protection for single-phase distribution circuits
- Electrical equipment and feeder protection
- AS/NZS IEC 60947-2:2015 is the applicable Australian/New Zealand product standard for low-voltage circuit-breakers of this type
- Installation and selection must comply with AS/NZS 3000:2018
- Verify the specific product's RCM and EESS status before installation or sale in Australia
- Long mechanical and electrical service life can reduce replacement frequency and component waste
- Metallic terminals and internal conductors can be recovered through appropriate electrical-equipment recycling
- Resettable overcurrent protection avoids routine replacement of fuses after fault operation
CHINT's general warranty policy lists 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels. Contractual or Australian distributor warranty terms may vary.
Available through authorised CHINT distributors in Australia.