MCCB 3P 125A 50kA Magnetic Only 250A Frame NM8N Chint
Chint NM8N 125A 3P MCCB features 50kA breaking capacity, magnetic-only trip unit for motor protection and a 250A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-250 Magnetic MCCB, 125A Motor Protection Circuit Breaker, 3-Phase Moulded Case Circuit Breaker
- Product Type: Moulded case circuit breaker (MCCB)
- Series: NM8N
- Frame Rating: 250A
- Rated Current: 125A
- Number of Poles: 3P
- Trip Unit: Magnetic-only motor protection
- Instantaneous Trip Setting: Adjustable from 7 to 12 times rated current for 125A to 160A units
- Ultimate Breaking Capacity (Icu): 50kA at 380/400/415V AC
- Service Breaking Capacity (Ics): 50kA at 380/400/415V AC
- Rated Operational Voltage: 380/400/415V, 440V, 500V and 660/690V AC
- Rated Insulation Voltage (Ui): 1,000V
- Rated Impulse Withstand Voltage (Uimp): 8kV
- Rated Frequency: 50/60Hz
- Utilisation Category: A
- Installation Type: Fixed mounting, front connection
- Dimensions (H x L x W): 157mm x 88.7mm x 105mm
- Weight: 1.85 kg
- Magnetic-only trip unit designed for motor protection applications
- 250A frame accommodates a 125A rated current
- 50kA short-circuit breaking capacity at standard three-phase supply voltages
- Adjustable instantaneous magnetic trip setting
- Suitable for isolation when installed in accordance with the applicable requirements
- Compact 3-pole design for switchboards and distribution assemblies
- Compatible with optional CHINT NM8N auxiliary and alarm accessories
- Installation, selection and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the switchboard manufacturer's requirements and the circuit breaker's installation instructions. Confirm fault level, conductor sizing, coordination and motor starting characteristics before installation.
- Motor feeder and motor control protection
- Switchboard mains and sub-mains protection
- Industrial and commercial distribution boards
- Three-phase equipment protection
- Short-circuit protection for motor circuits where thermal overload protection is provided separately or by the motor control system
- Designed and tested to IEC/EN 60947-2 for low-voltage circuit-breakers
- AS/NZS IEC 60947.2:2015 is the applicable Australian/New Zealand circuit-breaker standard for this product category
- Installation within a switchboard must also consider AS/NZS 3000 and the applicable AS/NZS 61439 requirements
- Resettable protection allows the breaker to be returned to service after a trip, reducing replacement waste compared with single-use protective devices
- Long mechanical and electrical service life can reduce product replacement frequency
- Metal components may be recoverable through appropriate electrical equipment recycling streams
CHINT warranty policy specifies 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels. Contractual or regional warranty conditions may vary.
Available through authorised CHINT distributors in Australia.