MCCB 3P 160A 100kA Thermal Magnetic 250A Frame NM8N Chint
Chint NM8N 160A 3P MCCB features 100kA breaking capacity, thermal-magnetic trip unit and a 250A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, MCCB, 3-Pole Circuit Breaker, Thermal-Magnetic Circuit Breaker, CHINT NM8N-250H TM 160 3P
- Rated Current: 160 A
- Frame Size: 250 A
- Number of Poles: 3P
- Breaking Capacity: 100 kA at 380/415 V AC
- Trip Unit: Adjustable thermal-magnetic
- Overload Adjustment: 0.7–1.0 × In
- Instantaneous Trip Adjustment: 7–12 × In for 125–160 A versions
- Rated Operational Voltage: 380/415 V AC
- Rated Frequency: 50/60 Hz
- Utilisation Category: Category A
- Connection: Fixed front connection
- Suitable for Isolation: Yes
- Product Standard Basis: IEC/EN 60947-2
- Dimensions (H x L x W): 157mm x 105mm x 88.7mm
- Weight: 0.9 kg
- High 100kA short-circuit breaking capacity
- Adjustable thermal overload and magnetic short-circuit protection
- Compact 250A frame with a 160A rated current
- Three-pole configuration for three-phase distribution systems
- Suitable for switchboard mains, sub-mains and commercial distribution protection
- Supports reliable isolation and overcurrent protection
- RoHS documentation is available for the NM8N series
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, applicable switchboard requirements and the manufacturer's instructions.
- Switchboard mains protection
- Sub-main and feeder protection
- Commercial and industrial low-voltage distribution boards
- Three-phase electrical distribution systems
- Backup protection and high prospective fault-current installations
- AS/NZS IEC 60947.2:2015 – applicable standard for low-voltage circuit-breakers
- AS/NZS 3000:2018 – electrical installation and selection requirements
- RoHS documentation supports restricted-substance compliance for the product range
- Durable moulded-case construction can extend service life and reduce replacement waste
- Metal and thermoplastic components may be recoverable through appropriate electrical equipment recycling streams
CHINT's general warranty policy covers other low-voltage apparatus for 27 months from the date of manufacture when sold through authorised channels; contract-specific terms may vary.
Available through authorised CHINT distributors in Australia.