MCCB 3P 160A 36kA Magnetic Only 250A Frame NM8N Chint

BRAND: CABAC
SKU: 271422
$2,117.50 List price: $2,823.30
+ −
Chint NM8N 160A 3P MCCB features 36kA breaking capacity, magnetic-only trip unit for motor protection and a 250A frame. Ideal for switchboard mains protection.

Alternatively Known As: 160A Magnetic-Only MCCB, Motor Protection MCCB, 3-Phase Moulded Case Circuit Breaker

Technical Specifications
  • Rated Current: 160A
  • Frame Size: 250A
  • Number of Poles: 3P
  • Trip Unit: Magnetic-only type for motor protection
  • Breaking Capacity: 36kA at 380/400/415V AC
  • Rated Operational Voltage: Up to 690V AC
  • Rated Insulation Voltage: 1000V
  • Rated Impulse Withstand Voltage: 8kV
  • Magnetic Trip Setting: 9–14 times rated current for motor protection
  • Utilisation Category: A
  • Standard Product Series: NM8N-250C M 160 3P
  • Manufacturer Standards: IEC 60947-1 and IEC 60947-2
  • Dimensions (H x L x W): 157mm x 88.7mm x 105mm
  • Weight: 1.85 kg
Key Features
  • Magnetic-only protection for motor circuits
  • 250A MCCB frame with a 160A rated current
  • Three-pole construction for three-phase systems
  • 36kA short-circuit breaking capacity
  • Suitable for motor starting and short-circuit protection
  • Compact fixed-mount MCCB design
  • Compatible with optional NM8N accessories including auxiliary contacts, shunt releases and undervoltage releases
  • Magnetic-only protection does not provide overload protection; use with a correctly selected overload relay where required
Professional Installation Requirements
  • Installation, commissioning and protection coordination must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and applicable switchboard requirements. Confirm that the magnetic-only trip characteristics and short-circuit rating are suitable for the motor circuit; separate overload protection is required where applicable.
Applications
  • Three-phase motor short-circuit protection
  • Industrial motor control panels
  • Commercial and industrial switchboards
  • Generator and machinery protection circuits
  • Distribution assemblies requiring magnetic-only MCCB protection
Standards & Compliance
  • AS/NZS IEC 60947.2:2015 is the applicable Australian/New Zealand product standard for low-voltage circuit breakers
  • AS/NZS 3000 applies to selection and installation within Australian electrical installations
  • AS/NZS 61439 may apply when the MCCB is installed as part of a low-voltage switchgear and controlgear assembly
Environmental Benefits
  • Long service life can reduce replacement frequency and electrical equipment waste
  • The MCCB is a durable, serviceable protection component that can remain in use when switchboard equipment is upgraded
  • RoHS documentation is available for the NM8N product family
Warranty Information

CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels, subject to the applicable terms and conditions.

Available Now

Available through authorised CHINT distributors in Australia.