MCCB 3P 160A 50kA Standard Electronic 250A Frame NM8N Chint
Chint NM8N 160A 3P MCCB features 50kA breaking capacity, standard electronic trip unit and a 250A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-250 EM 160A MCCB, 160A 3-Pole Moulded Case Circuit Breaker, Electronic MCCB
- Rated Current: 160 A
- Number of Poles: 3P
- Frame Size: 250 A
- Breaking Capacity: 50 kA at 415 V AC
- Trip Unit: Standard electronic EM type
- Long-Time Current Setting: 0.4–1.0 x In, adjustable in 1 A steps
- Short-Time Current Setting: 1.5–10 x Ir, adjustable or OFF
- Instantaneous Current Setting: 1.5–12 x In, adjustable or OFF
- Earth-Fault Protection: 0.4–1.0 x In, adjustable or OFF
- Rated Operational Voltage: 380/400/415 V AC, with higher-voltage ratings available by configuration
- Rated Insulation Voltage: 1,000 V
- Rated Impulse Withstand Voltage: 8 kV
- Rated Frequency: 50/60 Hz
- Utilisation Category: Category A
- Connection: Fixed mounting, suitable for isolation
- Dimensions (H x L x W): 157mm x 88.7mm x 105mm
- Weight: 2 kg
- Three-pole moulded case circuit breaker for low-voltage power distribution
- 50 kA short-circuit breaking capacity at 415 V AC
- 250 A frame with a 160 A rated current
- Standard electronic trip unit with overload, short-time, instantaneous and earth-fault protection
- Adjustable protection parameters for system coordination and selectivity
- Real-time current and fault information display
- Suitable for switchboard mains, sub-mains and commercial power distribution applications
- Compatible with NM8N accessories including auxiliary and alarm contacts, rotary handles and terminal shields
- Installation, configuration and commissioning must be performed by a licensed electrician or suitably qualified switchboard professional in accordance with the manufacturer's instructions, applicable electrical regulations and AS/NZS 3000. Protection settings should be selected and verified by a competent electrical professional for the installation.
- Switchboard mains protection
- Sub-main circuit protection
- Commercial and industrial power distribution
- Low-voltage distribution boards
- Protection of feeders, cables and electrical equipment
- Applications requiring adjustable electronic overcurrent and earth-fault protection
- AS/NZS IEC 60947.2:2015 for low-voltage circuit-breakers
- Metal components such as copper, aluminium and steel can be recovered and recycled at end of service life
- Adjustable electronic protection can support accurate system coordination and reduce unnecessary equipment replacement
- Durable moulded-case construction can extend service life and reduce material waste from premature replacement
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus, subject to authorised sales channels, applicable contract terms and the manufacturer's warranty conditions.
Available through authorised CHINT distributors in Australia.