MCCB 3P 180A 150kA Thermal Magnetic 250A Frame NM8N Chint
Chint NM8N 180A 3P MCCB features 150kA breaking capacity, thermal-magnetic trip unit and a 250A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N 250R MCCB, 3-Pole Moulded Case Circuit Breaker, Thermal-Magnetic Circuit Breaker
- Rated Current: 180 A
- Frame Size: 250 A
- Poles: 3P
- Trip Unit: Thermal-magnetic
- Ultimate Breaking Capacity Icu: 150 kA at AC 380–415 V
- Service Breaking Capacity Ics: 150 kA at AC 380–415 V
- Rated Operational Voltage: AC 380/400/415 V, 440 V, 500 V and 660/690 V
- Rated Insulation Voltage Ui: 1000 V
- Rated Impulse Withstand Voltage Uimp: 8 kV
- Rated Frequency: 50/60 Hz
- Utilisation Category: A
- Isolation: Suitable for isolation
- Product Standard: IEC/EN 60947-2
- Dimensions (H x L x W): 157mm x 88.7mm x 105mm
- Weight: 1.85 kg
- High 150kA short-circuit breaking capacity at AC 380–415V
- Thermal-magnetic overload and short-circuit protection
- 250A frame accommodates ratings from 125A to 250A
- Three-pole configuration for three-phase distribution systems
- Suitable for switchboard mains and sub-mains protection
- Suitable for isolation
- Designed for commercial, industrial and building-services power distribution
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with the manufacturer's instructions, AS/NZS 3000 and the requirements of the completed switchboard assembly. Verify prospective fault current, conductor ratings, discrimination and enclosure clearances before energising.
- Main switchboard incomer protection
- Sub-main circuit protection
- Commercial and industrial distribution boards
- Three-phase HVAC and mechanical-services equipment
- Building-services power distribution
- Overload and short-circuit protection for high-fault-level installations
- Applicable product standard: AS/NZS IEC 60947.2 for low-voltage circuit-breakers
- Installation should comply with AS/NZS 3000 Wiring Rules
- Switchboard integration should comply with the applicable AS/NZS 61439 requirements
- Thermal-magnetic protection can limit damage to downstream equipment and reduce premature component replacement
- Long mechanical and electrical service life helps reduce maintenance-related waste
- Moulded polymer housing and metallic conductive components can be separated for responsible end-of-life recycling where local facilities accept them
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels; contractual terms may vary.
Available through authorised CHINT distributors in Australia.