MCCB 3P 20A 50kA Magnetic Only 125A Frame NM8N Chint
Chint NM8N 20A 3P MCCB features 50kA breaking capacity, magnetic-only trip unit for motor protection and a 125A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N 20A MCCB, 3-Pole Magnetic Circuit Breaker, Motor Protection MCCB
- Product Series: NM8N-125S
- Rated Current: 20 A
- Number of Poles: 3P
- Frame Size: 125 A
- Release Type: Magnetic-only motor protection
- Magnetic Trip Setting: 240 A nominal
- Rated Operational Voltage: 380/400/415 V AC, with series ratings up to 690 V AC
- Rated Insulation Voltage: 1,000 V
- Rated Impulse Withstand Voltage: 8 kV
- Ultimate Breaking Capacity: 50 kA
- Service Breaking Capacity: 50 kA at applicable rated voltages
- Utilisation Category: A
- Installation: Fixed mounting with front or rear connection options
- Dimensions (H x L x W): 140mm x 78.5mm x 90mm
- Weight: 1.19 kg
- Three-pole moulded-case circuit breaker for low-voltage distribution systems
- Magnetic-only trip unit suited to motor circuit short-circuit protection
- 125A frame accommodates the 20A rated current configuration
- 50kA short-circuit breaking capacity
- Suitable for switchboards, motor feeders and industrial electrical equipment
- Supports vertical or horizontal installation and top or bottom line entry
- Zero arcing-distance design for enclosed switchboard applications
- Installation, selection and coordination should be performed by a licensed electrical contractor in accordance with AS/NZS 3000, the manufacturer's instructions and applicable switchboard requirements. Confirm magnetic trip coordination, prospective fault current, conductor sizing and required RCM/EESS compliance before installation.
- Motor feeder short-circuit protection
- Industrial switchboards
- Commercial electrical distribution boards
- Mains and sub-main protection where magnetic-only protection is specified
- Protection of electrical equipment and motor circuits
- AS/NZS IEC 60947.2: applicable low-voltage circuit-breaker standard
- AS/NZS 3000: applicable requirements for installation within Australian and New Zealand electrical installations
- Confirm product-specific RCM/EESS registration and marking before installation in Australia
- Durable moulded-case construction can support a long service life and reduce replacement waste
- Copper, aluminium and steel components used in electrical switchgear are recyclable through appropriate metal-recycling streams
- Magnetic-only protection avoids unnecessary thermal losses associated with some continuously energised electronic trip systems
CHINT warranty policy states that other low-voltage apparatus supplied through authorised sales channels is covered against defects in materials and workmanship for 27 months from the date of manufacture, subject to the applicable sales contract and warranty conditions.
Available through authorised CHINT distributors in Australia.