Alternatively Known As: Magnetic-only MCCB, moulded case circuit breaker, motor protection MCCB, CHINT NM8N 125H M 25A 3P
- Rated Current: 25 A
- Frame Size: 125 A
- Number of Poles: 3P
- Trip Unit: Magnetic-only electromagnetic release
- Breaking Capacity: 100 kA at 380/400/415 V AC
- Rated Operational Voltage: 380/400/415 V AC; maximum 690 V AC
- Rated Insulation Voltage: 1000 V AC
- Rated Impulse Withstand Voltage: 8 kV
- Frequency: 50/60 Hz
- Utilisation Category: Category A
- Electrical Endurance: 6,000 cycles
- Mechanical Endurance: 15,000 cycles
- Ingress Protection: IP40 when fitted with terminal covers; IP00 without covers
- Terminal Torque: 6.0 Nm using M6 terminals
- Product Reference: NM8N-125H M 25 3P
- Ordering Code: 271863
- Dimensions (H x L x W): 140mm x 78.5mm x 90mm
- Weight: 1.19 kg
- Magnetic-only trip unit for short-circuit protection in motor circuits
- Suitable for motor protection when used with a correctly selected overload relay
- High 100 kA short-circuit breaking capacity at 380/400/415 V AC
- Compact 125 A moulded-case frame with a 25 A magnetic release
- Three-pole construction for three-phase electrical systems
- Suitable for fixed, plug-in or DIN-rail mounting configurations where compatible accessories are used
- Supports front or rear connection arrangements
- Compatible with NM8N accessories including auxiliary contacts, alarm contacts, shunt release and undervoltage release
- Installation, selection and commissioning should be performed by a licensed electrician in accordance with the manufacturer's instructions, AS/NZS 3000 and the requirements of the switchboard assembly. A magnetic-only MCCB does not provide overload protection and should be coordinated with a suitable motor overload relay where required.
- Short-circuit protection for three-phase motors
- Motor control centres and industrial control panels
- Switchboard mains and submains protection
- Industrial power distribution boards
- Commercial and industrial low-voltage installations
- Applicable product standard: AS/NZS 60947.2 for low-voltage circuit-breakers
- CHINT product documentation specifies IEC/EN 60947-2; Australian certification and RCM requirements should be verified for the intended installation
- Installation in a switchboard assembly should also account for AS/NZS 61439 requirements
- Metal components, including copper conductors and steel mechanisms, are recyclable at end of service life
- Durable moulded-case construction and high mechanical endurance can reduce replacement frequency and material waste
- Magnetic-only motor protection can support appropriately coordinated motor systems and reduce damage caused by short-circuit events
CHINT's general warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to contract terms and exclusions for incorrect installation, misuse or unauthorised modification.