MCCB 3P 315A 36kA Magnetic Only 400A Frame NM8N Chint
Chint NM8N 315A 3P MCCB features 36kA breaking capacity, magnetic-only trip unit for motor protection and a 400A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-400C M 315 3P MCCB, Magnetic MCCB, Motor Protection Circuit Breaker
- Product Type: Moulded case circuit breaker
- Series: NM8N
- Frame Size: 400A
- Rated Current: 315A
- Number of Poles: 3P
- Release Type: Magnetic-only electromagnetic release
- Breaking Capacity: 36kA
- Rated Operational Voltage: Up to 690V AC
- Current Type: AC
- Protection Function: Short-circuit and instantaneous magnetic protection
- Installation Type: Fixed mounting
- Electrical Durability: Approximately 1500 operations
- Mechanical Durability: Approximately 15000 operations
- Dimensions (H x L x W): 250mm x 135mm x 140mm
- Weight: 5.735 kg
- Three-pole MCCB for low-voltage power distribution
- 400A frame with a 315A rated current
- 36kA short-circuit breaking capacity
- Magnetic-only release suited to motor protection applications
- Suitable for switchboard incomers, feeders and mains protection
- Compact moulded-case construction
- Auxiliary, alarm and shunt-trip accessories are available for the NM8N series
- Installation, selection and commissioning must be performed by a licensed electrician in accordance with applicable Australian electrical regulations, the manufacturer's instructions and AS/NZS 3000. Magnetic-only protection does not provide thermal overload protection, so a suitable overload relay or motor protection arrangement may be required.
- Motor circuit short-circuit protection
- Switchboard mains and incomer protection
- Industrial power distribution boards
- Commercial and industrial feeder protection
- Protection of high-current AC circuits
- Applicable product standard: AS/NZS IEC 60947.2 for low-voltage circuit-breakers
- Installations should comply with AS/NZS 3000 Wiring Rules
- Long service life can reduce replacement frequency and associated product waste
- Metal components and selected thermoplastic materials can be recovered through appropriate electrical equipment recycling streams
- Low contact resistance helps limit operating losses within the protected circuit
CHINT's general warranty policy for other low-voltage apparatus provides 27 months from the date of manufacture, subject to authorised sales channels and applicable contract terms.
Available through authorised CHINT distributors in Australia.