MCCB 3P 315A 70kA Magnetic Only 400A Frame NM8N Chint
Chint NM8N 315A 3P MCCB features 70kA breaking capacity, magnetic-only trip unit for motor protection and a 400A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-400Q M 315A 3P MCCB, Motor Protection MCCB, Magnetic-Only Moulded Case Circuit Breaker
- Rated Current: 315 A
- Frame Size: 400 A
- Number of Poles: 3P
- Trip Unit: Magnetic-only release for motor protection
- Breaking Capacity: 70 kA at 380–440 V AC
- Rated Operational Voltage: 380–415 V AC
- Rated Insulation Voltage: 1000 V
- Rated Impulse Withstand Voltage: 8 kV
- Ingress Protection: IP40
- Pollution Degree: 3
- Installation: Vertical or horizontal mounting; top or bottom line entry
- Product Reference: NM8N-400Q M 315 3P
- Dimensions (H x L x W): 255mm x 213mm x 140mm
- Weight: 5.25 kg
- High 70 kA short-circuit breaking capacity
- Magnetic-only trip unit designed for motor circuit short-circuit protection
- 400 A frame with a 315 A rated current
- Three-pole configuration for three-phase systems
- Suitable for industrial power distribution and switchboard applications
- Supports front, rear and plug-in connection accessories within the NM8N range
- Magnetic-only protection should be coordinated with a separate overload relay for motor applications
- Installation and commissioning must be performed by a licensed electrician in accordance with applicable electrical regulations, switchboard requirements and the manufacturer's instructions. Magnetic-only motor protection must be coordinated with a suitable overload protection device.
- Motor feeder short-circuit protection
- Industrial switchboards and distribution boards
- Three-phase commercial and industrial power distribution
- Large motor control and starter assemblies
- High-fault-level mains or sub-mains protection where separate overload protection is provided
- AS/NZS IEC 60947.2:2015 — applicable standard for low-voltage circuit-breakers
- AS/NZS 3000 — electrical installation and wiring requirements applicable to the installation
- Long service life can reduce replacement frequency and associated material waste
- Metal components can be recovered for recycling at end of service life
- CHINT NM8N product-family documentation includes RoHS declarations for restricted substances
- Efficient fault isolation helps limit damage to downstream electrical equipment
CHINT's general policy provides a 27-month warranty from the date of manufacture for other low-voltage apparatus sold through authorised sales channels, subject to the applicable contract and warranty conditions.
Available through authorised CHINT distributors in Australia.