MCCB 3P 32A 50kA Magnetic Only 125A Frame NM8N Chint
Chint NM8N 32A 3P MCCB features 50kA breaking capacity, magnetic-only trip unit for motor protection and a 125A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-125S M 32A 3P MCCB, Magnetic Motor Protection Circuit Breaker, Moulded Case Circuit Breaker
- Product Type: Moulded case circuit breaker
- Frame Size: 125A
- Rated Current: 32A
- Number of Poles: 3P
- Trip Unit: Magnetic only
- Magnetic Trip Setting: 384A nominal, approximately 12 times rated current
- Breaking Capacity: 50kA, S breaking-capacity class
- Rated Operational Voltage: Up to 690V AC, 50/60Hz
- Rated Insulation Voltage: 1000V
- Rated Impulse Withstand Voltage: 8kV
- Utilisation Category: A
- Connection: Fixed front or rear connection options
- Installation Position: Vertical or horizontal
- Mechanical Life: Up to 25,000 switching cycles
- Electrical Life: Up to 2,000 cycles at 690V AC and rated current
- Standard Product Classification: IEC/EN 60947-2
- Dimensions (H x L x W): 140mm x 78.5mm x 90mm
- Weight: 1.19 kg
- Three-pole MCCB with a compact 125A frame
- Magnetic-only trip unit suited to motor starting and short-circuit protection
- 50kA ultimate breaking capacity for high-fault-level installations
- Adjustable magnetic release setting of approximately 384A
- Suitable for AC systems up to 690V
- Supports front or rear connection arrangements
- Suitable for fixed installation and switchboard integration
- Designed for circuit, equipment and motor protection
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and applicable local electrical requirements. Magnetic-only protection does not provide overload protection, so coordinated motor overload protection may be required.
- Motor feeder short-circuit protection
- Motor control centres and industrial control panels
- Commercial and industrial switchboards
- Main or sub-main circuit protection where magnetic-only tripping is specified
- Electrical equipment and distribution circuits requiring high fault interruption capacity
- AS/NZS 60947.2 for low-voltage circuit-breakers
- AS/NZS 3000 for installation within Australian low-voltage electrical installations
- Moulded-case construction includes recyclable copper and ferrous metal components
- Long mechanical and electrical service life can reduce replacement frequency and product waste
- CHINT publishes RoHS documentation for the NM8N product family, supporting restricted-substance compliance
- Provides reliable fault protection that can help reduce damage to downstream electrical equipment
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels, subject to the applicable contract and warranty conditions.
Available through authorised CHINT distributors in Australia.