MCCB 3P 400A 150kA Magnetic Only 400A Frame NM8N Chint
Chint NM8N 400A 3P MCCB features 150kA breaking capacity, magnetic-only trip unit for motor protection and a 400A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N-400R M 400A 3P MCCB, Magnetic Motor Protection Circuit Breaker, 400A Moulded Case Circuit Breaker
- Frame Size: 400A
- Rated Current: 400A
- Number of Poles: 3P
- Trip Unit: Magnetic-only electromagnetic release
- Rated Ultimate Breaking Capacity Icu: 150kA at 380/400/415V AC; 100kA at 440V AC
- Rated Service Breaking Capacity Ics: 150kA at 380/400/415V AC; 100kA at 440V AC
- Magnetic Trip Setting: 9–14 x In for motor protection
- Rated Operational Voltage: 380/400/415/440V AC
- Rated Insulation Voltage Ui: 1,000V
- Rated Impulse Withstand Voltage Uimp: 12kV
- Mechanical Endurance: 15,000 operations
- Electrical Endurance: 1,500 operations
- Connection Type: Fixed-mounted MCCB
- Dimensions (H x L x W): 250mm x 135mm x 140mm
- Weight: 5 kg
- 150kA high short-circuit breaking capacity at 380–415V AC
- Magnetic-only trip unit designed for motor short-circuit protection
- 400A frame with 400A rated current
- Three-pole configuration for three-phase systems
- Adjustable instantaneous magnetic trip setting from 9–14 times rated current
- Suitable for use with a contactor and separate thermal overload relay in motor protection arrangements
- Moulded case construction for low-voltage power distribution and industrial switchboards
- Installation, selection, fault-level verification and commissioning must be performed by a licensed electrician in accordance with applicable Australian wiring rules, manufacturer instructions and switchboard requirements. Because this is magnetic-only protection, a separate overload protection device is required where motor overload protection is needed.
- Three-phase motor short-circuit protection
- Industrial motor control centres and switchboards
- High-fault-level switchboard feeders
- Power distribution systems requiring magnetic-only MCCB protection
- Motor protection systems using a contactor and separate thermal overload relay
- AS/NZS IEC 60947.2:2015 is the applicable Australian/New Zealand product standard for low-voltage circuit-breakers; verify certification and Regulatory Compliance Marking for the supplied unit
- Installation should comply with AS/NZS 3000 wiring requirements
- Long mechanical and electrical endurance can reduce replacement frequency and associated waste
- Copper and other metallic components can be recovered through established electrical equipment recycling streams
- Reusable accessory and switchboard-compatible construction can support equipment refurbishment rather than complete replacement
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to contract terms and warranty conditions.
Available through authorised CHINT distributors in Australia.