MCCB 3P 40A 100kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 40A 3P MCCB features 100kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, MCCB, Thermal-Magnetic Circuit Breaker, 3P 40A Circuit Breaker
- Rated Current: 40 A
- Number of Poles: 3P
- Frame Size: 125 A
- Trip Unit: Thermal-magnetic, TM
- Ultimate Short-Circuit Breaking Capacity: 100 kA at 380/400/415 V AC
- Rated Operational Voltage: Up to 690 V AC, 50/60 Hz
- Rated Insulation Voltage: 1000 V AC
- Rated Impulse Withstand Voltage: 8 kV
- Utilisation Category: A
- Adjustable Thermal Trip Range: 0.7–1.0 x In
- Mechanical Life: Up to 25,000 operating cycles
- Electrical Life: Up to 10,000 operating cycles at 415 V AC
- Mounting: Fixed front or rear connection options
- Dimensions (H x L x W): 140mm x 78.5mm x 90mm
- Weight: 1.19 kg
- 100 kA high short-circuit breaking capacity at 380–415 V AC
- Thermal-magnetic protection for overload and short-circuit conditions
- Compact 125 A frame suitable for switchboard integration
- Three-pole configuration for three-phase distribution systems
- Adjustable thermal trip setting from 0.7 to 1.0 times rated current
- Suitable for isolation and low-voltage power distribution applications
- Maintenance-free mechanism with long mechanical operating life
- Installation, selection and commissioning should be performed by a licensed electrician in accordance with applicable Australian electrical regulations, AS/NZS 3000 and the manufacturer's installation instructions. Confirm fault levels, conductor ratings, discrimination and local certification requirements before installation.
- Switchboard mains protection
- Sub-mains protection
- Commercial and industrial low-voltage distribution boards
- Three-phase feeders and outgoing circuits
- Power distribution in industrial buildings and infrastructure
- Protection of electrical equipment against overload and short circuit
- Applicable Australian/New Zealand product standard: AS/NZS 60947.2 for low-voltage circuit-breakers
- CHINT specifies IEC/EN 60947-2 for the NM8N series; verify Australian certification and RCM requirements for the specific supplied variant
- Long mechanical and electrical service life can reduce replacement frequency and equipment waste
- Metal components may be recovered through appropriate electrical equipment recycling streams
- Thermal-magnetic protection helps limit damage to downstream equipment during overload and short-circuit events
CHINT's general warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels. Contractual terms and local distributor conditions may vary.
Available through authorised CHINT distributors in Australia.