MCCB 3P 500A 36kA Magnetic Only 800A Frame NM8N Chint
Chint NM8N 500A 3P MCCB features 36kA breaking capacity, magnetic-only trip unit for motor protection and a 800A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: NM8N-800C M 500 3P MCCB, 500A Motor Protection Circuit Breaker, Magnetic MCCB, Moulded Case Circuit Breaker
- Product Type: Moulded case circuit breaker
- Frame Size: 800A
- Rated Current: 500A
- Number of Poles: 3P
- Release Type: Magnetic-only, M type
- Breaking Capacity: 36kA, C breaking-capacity code
- Magnetic Trip Adjustment: 9–14 times rated current
- Rated Operational Voltage: Up to 690VAC, subject to configuration
- Rated Insulation Voltage: 1000V
- Rated Impulse Withstand Voltage: 12kV
- Mechanical Durability: 15,000 operations
- Electrical Durability: 1,500 operations
- Installation: Fixed type with front or rear connection options
- Applicable Product Standard: IEC/EN 60947-2
- Dimensions (H x L x W): 300mm x 133mm x 195mm
- Weight: 9.5 kg
- 500A rated current in an 800A frame
- Three-pole configuration for three-phase systems
- Magnetic-only trip unit intended for motor protection arrangements
- 36kA short-circuit breaking capacity
- Adjustable magnetic instantaneous protection
- Suitable for industrial switchboards and high-current distribution assemblies
- Can be installed vertically or horizontally with top or bottom line entry
- Compatible with selected auxiliary, alarm, shunt-trip and undervoltage accessories
- Installation, commissioning and maintenance must be carried out by a licensed electrician in accordance with the approved switchboard design, manufacturer instructions, AS/NZS 3000 and applicable high-current electrical safety requirements. The magnetic-only release does not provide thermal overload protection, so a correctly selected thermal overload relay is required for motor protection systems.
- Industrial switchboard mains protection
- Three-phase motor protection using a contactor and separate thermal overload relay
- High-current power distribution
- Commercial and industrial electrical distribution boards
- Short-circuit protection for large motor control assemblies
- AS/NZS IEC 60947.2:2015 — applicable Australian/New Zealand standard for low-voltage circuit-breakers; verify product-specific conformity documentation before installation
- AS/NZS 3000:2018 — electrical installation requirements applicable to the surrounding installation and switchboard
- Durable moulded-case construction can support a long service life and reduce replacement waste
- Metal components and copper conductors are recyclable at end of service life
- RoHS documentation is available for the NM8N product series, subject to the supplied product configuration
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus, including MCCBs, when purchased through authorised sales channels. Contract terms and regional conditions may vary.
Available through authorised CHINT distributors in Australia.