MCCB 3P 500A 50kA Thermal Magnetic 800A Frame NM8N Chint
Chint NM8N 500A 3P MCCB features 50kA breaking capacity, thermal-magnetic trip unit and a 800A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, MCCB, Thermal-Magnetic Circuit Breaker, NM8N-800S TM 500A 3P
- Product Series: NM8N-800S
- Rated Current: 500A
- Frame Size: 800A
- Number of Poles: 3P
- Trip Unit: Thermal-magnetic, adjustable
- Overload Trip Adjustment: 350–500A
- Rated Operational Voltage: Up to 690V AC
- Rated Insulation Voltage: 1,000V AC
- Rated Impulse Withstand Voltage: 8kV
- Ultimate Breaking Capacity Icu: 50kA at 380/400/415V AC
- Service Breaking Capacity Ics: 50kA at 380/400/415V AC
- Utilisation Category: Category A
- Installation: Vertical or horizontal mounting; top or bottom line entry
- Ingress Protection: IP40 with terminal covers
- Mechanical Durability: Up to 10,000 operating cycles
- Product Standard: IEC 60947-2
- Dimensions (H x L x W): 300mm x 133mm x 195mm
- Weight: 10.12 kg
- 500A rated current in an 800A frame
- Three-pole configuration for three-phase distribution systems
- 50kA short-circuit breaking capacity at 380/400/415V AC
- Thermal-magnetic protection for overload and short-circuit conditions
- Adjustable overload trip range from 350A to 500A
- Suitable for main switchboard and sub-main protection
- Compatible with optional auxiliary, shunt-trip, undervoltage, motor operator and terminal accessories
- Can be installed vertically or horizontally
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and the requirements of the switchboard assembly. Confirm prospective fault current, cable ratings, discrimination and enclosure clearances before energising.
- Main switchboard incomer protection
- Sub-main distribution protection
- Commercial and industrial switchboards
- Power distribution centres
- Motor control and industrial distribution equipment
- Data centre and infrastructure power distribution
- AS/NZS IEC 60947.2:2015 is the applicable Australian/New Zealand product standard for low-voltage circuit-breakers; verify the specific installation's RCM, certification and switchboard requirements before use.
- AS/NZS 3000:2018 applies to electrical installation selection, connection and protection requirements.
- Long service life and high mechanical durability can reduce replacement frequency and associated waste.
- Metallic and thermoplastic components may be recoverable through appropriate electrical equipment recycling streams at end of life.
- RoHS compliance is declared for the NM8N product range, helping restrict certain hazardous substances in electrical equipment.
CHINT's published general policy provides a 27-month warranty from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable contract and warranty exclusions.
Available through authorised CHINT distributors in Australia.