MCCB 3P 50A 70kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 50A 3P MCCB features 70kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, Thermal-Magnetic MCCB, 3-Phase Circuit Breaker, NM8N-125Q TM 50A 3P
- Product Type: Moulded Case Circuit Breaker
- Series: NM8N
- Rated Current: 50 A
- Number of Poles: 3P
- Frame Size: 125 A
- Trip Unit: Adjustable thermal-magnetic, TM
- Breaking Capacity: 70 kA Icu
- Overload Adjustment Range: 35–50 A
- Rated Operational Voltage: 380/415 V AC
- Rated Insulation Voltage: 1,000 V
- Frequency: 50/60 Hz
- Protection Rating: IP40
- Utilisation Category: A
- Mechanical Life: 15,000 operating cycles
- Connection: Fixed front connection
- Installation Orientation: Vertical or horizontal mounting; top or bottom line entry
- Dimensions (H x L x W): 140mm x 78.5mm x 90mm
- Weight: 1.19 kg
- 70 kA ultimate short-circuit breaking capacity
- Adjustable thermal-magnetic overload and short-circuit protection
- Three-pole configuration for three-phase circuits
- Compact 125 A frame suitable for switchboard assemblies
- Suitable for mains, sub-mains and distribution protection
- Supports front connection and flexible installation orientation
- Maintenance-free operating mechanism
- Installation, testing and commissioning must be performed by a licensed electrical contractor in accordance with AS/NZS 3000, the switchboard manufacturer's requirements and applicable local regulations. Confirm prospective fault current, discrimination, cable capacity and required Australian conformity markings before installation.
- Switchboard mains protection
- Sub-main protection
- Three-phase distribution boards
- Commercial and industrial power distribution
- Motor and equipment feeder protection where the thermal-magnetic characteristics are suitable
- Short-circuit and overload protection in low-voltage AC installations
- AS/NZS IEC 60947.2:2015 is the applicable Australian/New Zealand product standard for low-voltage circuit-breakers
- Installations should comply with AS/NZS 3000:2018 and applicable amendments
- Verify Australian regulatory acceptance, including required RCM marking, before installation
- Reusable protective device with a long mechanical service life, helping reduce replacement frequency and equipment waste
- Metal and thermoplastic components may be recoverable through suitable electrical equipment recycling streams at end of life
- Helps limit damage to downstream electrical equipment during overload and short-circuit events
CHINT warranty policy states 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable customer contract and warranty conditions.
Available through authorised CHINT distributors in Australia.