MCCB 3P 630A 100kA Magnetic Only 800A Frame NM8N Chint
Chint NM8N 630A 3P MCCB features 100kA breaking capacity, magnetic-only trip unit for motor protection and a 800A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N 800H magnetic-only moulded case circuit breaker, 630A 3-pole MCCB, motor protection MCCB
- Product Code: 273082
- Device Type: Moulded case circuit breaker
- Frame Size: 800A
- Rated Current: 630A
- Number of Poles: 3P
- Release Type: Magnetic-only release
- Breaking Capacity: 100kA at 380/400/415V AC
- Rated Operational Voltage: 380/400/415V AC, with operation up to 690V AC depending on system configuration
- Rated Insulation Voltage: 1000V
- Rated Impulse Withstand Voltage: 12kV
- Rated Service Breaking Capacity: 100% of Icu
- Utilisation Category: A
- Mechanical Durability: Up to 15,000 operating cycles
- Electrical Durability: Up to 1,500 operating cycles
- Ambient Temperature: -40°C to +70°C
- Standard Declared by Manufacturer: IEC 60947-2
- Dimensions (H x L x W): 300mm x 133mm x 195mm
- Weight: 13 kg
- 630A magnetic-only trip rating in an 800A frame
- 100kA ultimate short-circuit breaking capacity at 380/400/415V AC
- Three-pole construction for three-phase distribution systems
- Magnetic-only protection suited to motor circuits when overload protection is provided separately
- Adjustable magnetic trip protection for short-circuit protection
- Suitable for switchboards, power distribution and motor control applications
- Supports front, rear and plug-in connection arrangements subject to accessories and configuration
- Modular accessory system for auxiliary, alarm, shunt-trip and undervoltage functions
- Installation, selection of trip settings and commissioning must be performed by a licensed electrician or suitably qualified switchboard professional. The magnetic-only release does not provide thermal overload protection, so a correctly coordinated motor overload relay or electronic motor protection device is required where applicable. Installation must comply with the applicable wiring rules, fault-level calculations, manufacturer instructions and switchboard assembly requirements.
- Switchboard mains and feeder protection
- Industrial power distribution
- Motor control centres with separate overload protection
- Large motor short-circuit protection
- Commercial and industrial switchboards
- Three-phase low-voltage electrical installations
- AS/NZS 60947.2: Applicable Australian/New Zealand product standard for low-voltage circuit-breakers; product-specific Australian certification and RCM status should be verified before installation.
- Long service life and high mechanical endurance can reduce replacement frequency and product waste
- Metallic conductive components and the moulded enclosure can be recovered through appropriate electrical equipment recycling streams
- Modular accessories allow selected components to be replaced or upgraded without replacing the complete breaker
- Supports reliable system protection, helping reduce damage and waste caused by electrical faults
CHINT warranty policy specifies 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable customer contract and warranty conditions.
Available through authorised CHINT distributors in Australia.