SCHNAP Logo

Making Trade Life Easy!
Trade Discount 25%

MCCB 3P 630A 50kA Magnetic Only 800A Frame NM8N Chint

BRAND: CABAC
SKU: 273074
$6,544.40 List price: $8,725.90
+ −
Chint NM8N 630A 3P MCCB features 50kA breaking capacity, magnetic-only trip unit for motor protection and a 800A frame. Ideal for switchboard mains protection.

Alternatively Known As: CHINT NM8N-800S M 630A 3P MCCB, Magnetic Motor Protection Circuit Breaker, Moulded Case Circuit Breaker

Technical Specifications
  • Product Type: Moulded case circuit breaker
  • Series: NM8N
  • Frame Size: 800A
  • Rated Current: 630A at 40°C
  • Number of Poles: 3P
  • Breaking Capacity: 50kA at AC 380/400/415V
  • Rated Operational Voltage: Up to 690V AC, 50/60Hz
  • Rated Insulation Voltage: 1000V
  • Rated Impulse Withstand Voltage: 8kV
  • Trip Unit: Magnetic-only release for motor protection
  • Utilisation Category: Category A
  • Mounting: Fixed installation with front or rear connection options
  • Mechanical Durability: Up to 25,000 operating cycles
  • Electrical Durability: Up to 10,000 cycles at AC 415V
  • Standard: IEC/EN 60947-2
  • Dimensions (H x L x W): 300mm x 133mm x 195mm
  • Weight: 9.5 kg
Key Features
  • 630A rated current in an 800A frame
  • 50kA short-circuit breaking capacity at AC 380/400/415V
  • Magnetic-only trip unit designed for motor protection applications
  • Three-pole configuration for three-phase power systems
  • Suitable for fixed switchboard and industrial distribution installations
  • High insulation and impulse withstand ratings
  • Modular accessory system for selected auxiliary, shunt and undervoltage releases
  • Suitable for isolation when installed and applied in accordance with manufacturer requirements
Professional Installation Requirements
  • Installation, selection and commissioning should be performed by a licensed electrician in accordance with AS/NZS 3000, applicable switchboard requirements and the manufacturer's instructions. Magnetic-only protection does not provide thermal overload protection and must be coordinated with the motor protection system.
Applications
  • Motor feeder short-circuit protection
  • Industrial switchboards and motor control centres
  • Three-phase power distribution
  • Switchboard mains and sub-mains protection where the protection scheme is correctly coordinated
  • Commercial and industrial electrical installations
Standards & Compliance
  • AS/NZS IEC 60947.2 for low-voltage circuit-breakers
  • AS/NZS 3000 for electrical installation and wiring requirements
Environmental Benefits
  • Robust moulded-case construction can support a long service life and reduce replacement waste
  • Copper and metallic conductive materials can be recovered through established electrical equipment recycling streams
  • Suitable application in efficient, properly coordinated motor and power distribution systems can help minimise avoidable electrical losses
  • Replaceable accessories and serviceable construction can extend the useful life of the breaker
Warranty Information

CHINT warranty policy generally covers other low-voltage apparatus for 27 months from the date of manufacture when purchased through authorised sales channels, subject to the applicable contract and warranty conditions.

Available Now

Available through authorised CHINT distributors in Australia.