MCCB 3P 63A 100kA Magnetic Only 125A Frame NM8N Chint
Chint NM8N 63A 3P MCCB features 100kA breaking capacity, magnetic-only trip unit for motor protection and a 125A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N 125AF Motor Protection MCCB, 3-Pole Magnetic Circuit Breaker, NM8N-125H M 63 3P
- Product Type: Moulded case circuit breaker
- Frame Size: 125A frame
- Rated Current: 63A
- Number of Poles: 3P
- Release Type: Magnetic-only release for motor protection
- Rated Operational Voltage: 380–415V AC
- Rated Frequency: 50/60Hz
- Ultimate Breaking Capacity Icu: 100kA at 380/400/415V AC
- Service Breaking Capacity Ics: 100% of Icu
- Instantaneous Magnetic Trip Setting: 12 × In for the 63A motor-protection variant
- Magnetic Trip Accuracy: ±20%
- Utilisation Category: A
- Ingress Protection: IP40 when fitted with terminal covers
- Connection: Screw terminals
- Installation: Surface mounting with screw fixing
- Applicable Product Standard: IEC/EN 60947-2
- Dimensions (H x L x W): 140mm x 90mm x 78.5mm
- Weight: 1.05 kg
- 100kA short-circuit breaking capacity
- Magnetic-only trip unit designed for motor circuit protection
- 125A frame with a 63A rated current
- Three-pole configuration for three-phase systems
- Suitable for 380–415V AC applications at 50/60Hz
- Compatible with optional shunt trip, undervoltage release, auxiliary contact and alarm contact accessories
- Designed for vertical or horizontal installation with top or bottom line entry
- Magnetic-only protection should be used with a suitable overload or thermal relay for complete motor protection
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and applicable switchboard requirements. A separate overload protection device is required where motor overload protection is not provided elsewhere.
- Three-phase motor short-circuit protection
- Motor control centres and industrial control panels
- Switchboard outgoing motor feeders
- Industrial power distribution systems
- Commercial and industrial electrical equipment protection
- Applicable Australian/New Zealand product standard: AS/NZS IEC 60947.2 for low-voltage circuit-breakers; confirm product approval and RCM requirements before installation.
- Electrical installation and switchboard integration should comply with AS/NZS 3000 and applicable assembly requirements.
- Long service life can reduce replacement frequency and associated material waste
- Metallic and polymer components may be recoverable for recycling at end of service life, subject to local recycling facilities
- Supports reliable motor protection, which can help reduce equipment damage and premature replacement
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels, subject to the applicable sales contract and warranty conditions.
Available through authorised CHINT distributors in Australia.