MCCB 3P 63A 50kA Standard Electronic 250A Frame NM8N Chint
Chint NM8N 63A 3P MCCB features 50kA breaking capacity, standard electronic trip unit and a 250A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: CHINT NM8N 250A Frame MCCB, 63A 3P Electronic MCCB, Moulded Case Circuit Breaker, Switchboard Main Circuit Breaker
- Rated Current: 63A
- Number of Poles: 3P
- Frame Size: 250A
- Breaking Capacity: 50kA at 380/400/415V AC
- Release Type: EM standard electronic trip unit
- Rated Operational Voltage: 380/400/415V AC, up to 690V AC
- Rated Insulation Voltage: 1000V AC
- Rated Impulse Withstand Voltage: 8kV
- Utilisation Category: A
- Operating Frequency: 50/60Hz
- Mounting: Fixed, front or rear connection; DIN-rail mounting with adapter
- Operating Temperature: -25°C to +70°C for standard electronic release
- Standard Product Design: IEC/EN 60947-2
- Dimensions (H x L x W): 157mm x 88.7mm x 105mm
- Weight: 2 kg
- Three-pole protection for three-phase distribution systems
- 50kA short-circuit breaking capacity at common low-voltage supply ratings
- 250A frame accommodates a broad range of electronic trip ratings
- Standard electronic trip unit provides accurate overload and short-circuit protection
- Suitable for switchboard mains and sub-mains protection
- Can be installed with top or bottom line entry
- Modular accessory system supports auxiliary and signalling functions
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and applicable switchboard requirements. Confirm fault level, discrimination, cable ratings and local approval requirements before installation.
- Main switchboard protection
- Sub-main circuit protection
- Commercial and industrial power distribution
- Three-phase building services
- Motor control and distribution boards where the selected electronic protection settings are suitable
- Applicable product standard: AS/NZS IEC 60947.2:2015 for low-voltage circuit-breakers
- Electrical installation and switchboard integration should comply with AS/NZS 3000 and applicable local regulatory requirements
- Long service life reduces replacement frequency and associated material waste
- Copper and aluminium conductors used with the breaker are recyclable at end of service life
- Electronic protection can support accurate fault isolation and reduce damage to downstream electrical equipment
- Product documentation includes RoHS-related declarations for the NM8N series
CHINT warranty policy specifies 27 months from the date of manufacture for other low-voltage apparatus purchased through authorised sales channels, subject to the applicable sales contract and exclusions for improper installation, misuse or unauthorised modification.
Available through authorised CHINT distributors in Australia.