SCHNAP Logo

Making Trade Life Easy!
Trade Discount 25%

MCCB 3P 63A 50kA Standard Electronic 250A Frame NM8N Chint

BRAND: CABAC
SKU: 271382
$1,058.80 List price: $1,411.70
+ −
Chint NM8N 63A 3P MCCB features 50kA breaking capacity, standard electronic trip unit and a 250A frame. Ideal for switchboard mains and sub-mains protection.

Alternatively Known As: CHINT NM8N 250A Frame MCCB, 63A 3P Electronic MCCB, Moulded Case Circuit Breaker, Switchboard Main Circuit Breaker

Technical Specifications
  • Rated Current: 63A
  • Number of Poles: 3P
  • Frame Size: 250A
  • Breaking Capacity: 50kA at 380/400/415V AC
  • Release Type: EM standard electronic trip unit
  • Rated Operational Voltage: 380/400/415V AC, up to 690V AC
  • Rated Insulation Voltage: 1000V AC
  • Rated Impulse Withstand Voltage: 8kV
  • Utilisation Category: A
  • Operating Frequency: 50/60Hz
  • Mounting: Fixed, front or rear connection; DIN-rail mounting with adapter
  • Operating Temperature: -25°C to +70°C for standard electronic release
  • Standard Product Design: IEC/EN 60947-2
  • Dimensions (H x L x W): 157mm x 88.7mm x 105mm
  • Weight: 2 kg
Key Features
  • Three-pole protection for three-phase distribution systems
  • 50kA short-circuit breaking capacity at common low-voltage supply ratings
  • 250A frame accommodates a broad range of electronic trip ratings
  • Standard electronic trip unit provides accurate overload and short-circuit protection
  • Suitable for switchboard mains and sub-mains protection
  • Can be installed with top or bottom line entry
  • Modular accessory system supports auxiliary and signalling functions
Professional Installation Requirements
  • Installation, testing and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, the manufacturer's instructions and applicable switchboard requirements. Confirm fault level, discrimination, cable ratings and local approval requirements before installation.
Applications
  • Main switchboard protection
  • Sub-main circuit protection
  • Commercial and industrial power distribution
  • Three-phase building services
  • Motor control and distribution boards where the selected electronic protection settings are suitable
Standards & Compliance
  • Applicable product standard: AS/NZS IEC 60947.2:2015 for low-voltage circuit-breakers
  • Electrical installation and switchboard integration should comply with AS/NZS 3000 and applicable local regulatory requirements
Environmental Benefits
  • Long service life reduces replacement frequency and associated material waste
  • Copper and aluminium conductors used with the breaker are recyclable at end of service life
  • Electronic protection can support accurate fault isolation and reduce damage to downstream electrical equipment
  • Product documentation includes RoHS-related declarations for the NM8N series
Warranty Information

CHINT warranty policy specifies 27 months from the date of manufacture for other low-voltage apparatus purchased through authorised sales channels, subject to the applicable sales contract and exclusions for improper installation, misuse or unauthorised modification.

Available Now