MCCB 3P 700A 100kA Thermal Magnetic 800A Frame NM8N Chint
Chint NM8N 700A 3P MCCB features 100kA breaking capacity, thermal-magnetic trip unit and a 800A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: 700A Thermal-Magnetic MCCB, 800A Frame Moulded Case Circuit Breaker, NM8N-800H TM 700 3P
- Product Type: Moulded case circuit breaker
- Frame Size: 800A
- Rated Current: 700A
- Number of Poles: 3P
- Trip Unit: Thermal-magnetic, TM
- Breaking Capacity: 100kA, H class
- Rated Voltage: AC up to 690V; DC up to 1000V
- Rated Frequency: 50/60Hz
- Rated Insulation Voltage: 1000V
- Rated Impulse Withstand Voltage: 12kV
- Installation: Fixed mounting with front connection
- Terminal Configuration: Six M12 terminals
- Protection Function: Overload and short-circuit protection
- Dimensions (H x L x W): 300mm x 113mm x 140mm
- Weight: 9.5 kg
- High 100kA short-circuit breaking capacity
- 700A rated current within an 800A frame
- Three-pole configuration for three-phase distribution systems
- Thermal-magnetic protection for dependable overload and fault interruption
- Suitable for switchboard mains and sub-mains protection
- Can be installed vertically or horizontally with line entry from the top or bottom
- Suitable for isolation when correctly installed and applied
- Installation, configuration and commissioning must be performed by a licensed electrician in accordance with AS/NZS 3000, applicable switchboard requirements and the manufacturer's instructions. Confirm prospective fault current, cable capacity, discrimination and local RCM requirements before installation.
- Main incoming protection in commercial and industrial switchboards
- Sub-main protection and distribution boards
- Three-phase building power distribution
- Industrial plant and machinery feeders
- Data centre, infrastructure and high fault-level electrical distribution systems
- AS/NZS IEC 60947.2:2015 is the applicable Australian/New Zealand product standard for low-voltage circuit-breakers; confirm product certification and RCM suitability for the intended installation.
- AS/NZS 3000 applies to selection, installation and verification within Australian electrical installations.
- AS/NZS 61439 applies to the design, assembly and verification of compatible low-voltage switchboards and assemblies.
- Long service life can reduce replacement frequency and associated material waste.
- Steel, copper and aluminium components used in electrical switchgear are recyclable through appropriate recovery streams.
- Thermal-magnetic protection helps prevent damage to downstream equipment, reducing premature equipment replacement.
CHINT warranty policy covers other low-voltage apparatus, including MCCBs, against defects in materials and workmanship for 27 months from the date of manufacture when sold through authorised sales channels. Contract-specific terms may apply.
Available through authorised CHINT distributors in Australia.