MCCB 3P 700A 150kA Magnetic Only 800A Frame NM8N Chint
Chint NM8N 700A 3P MCCB features 150kA breaking capacity, magnetic-only trip unit for motor protection and a 800A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: 700A magnetic-only moulded case circuit breaker, 3-pole MCCB, motor protection MCCB, NM8N-800R-M
- Rated Current: 700 A
- Number of Poles: 3P
- Frame Size: 800 A
- Trip Unit: Magnetic type, motor protection
- Ultimate Breaking Capacity Icu: 150 kA at AC 380/400/415 V
- Service Breaking Capacity Ics: 150 kA at AC 380/400/415 V
- Magnetic Trip Setting: 9–14 x In, adjustable
- Magnetic Trip Range: 6,300–9,800 A
- Rated Operational Voltage: 380/400/415 VAC; up to 690 VAC depending on breaking-capacity rating
- Rated Insulation Voltage: 1,000 V
- Utilisation Category: A
- Installation: Fixed mounting with front or rear connection
- Ambient Temperature: -40°C to +70°C
- Ingress Protection: IP40
- Applicable Product Standard: IEC/EN 60947-2
- Dimensions (H x L x W): 250mm x 135mm x 140mm
- Weight: 2.4 kg
- 150 kA short-circuit breaking capacity at AC 380/400/415 V
- Magnetic-only trip unit designed for motor protection systems
- 800 A frame accommodates a 700 A rated current
- Adjustable instantaneous magnetic trip setting from 9 to 14 times rated current
- Suitable for switchboard mains, feeder and high-current motor protection
- Supports isolation and front or rear connection arrangements
- Maintenance-free construction with high mechanical endurance
- Installation, testing and commissioning must be performed by a licensed electrician in accordance with applicable electrical installation requirements, manufacturer instructions and AS/NZS 3000. Protection settings must be selected to suit the connected equipment and fault level.
- Switchboard mains protection
- High-current feeder protection
- Industrial motor protection systems used with a contactor and thermal overload relay
- Commercial and industrial power distribution
- Backup and short-circuit protection for low-voltage switchboards
- AS/NZS IEC 60947.2:2015 for low-voltage circuit-breakers
- AS/NZS 3000:2018 for installation within Australian electrical installations
- Long service life can reduce replacement frequency and electrical equipment waste
- Metal conductive parts and thermoplastic components can be recovered through appropriate electrical equipment recycling streams
- Supports reliable system protection, helping reduce damage and premature replacement of downstream electrical equipment
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised channels, subject to the applicable customer contract and warranty conditions.
Available through authorised CHINT distributors in Australia.