MCCB 3P 700A 50kA Magnetic Only 800A Frame NM8N Chint
Chint NM8N 700A 3P MCCB features 50kA breaking capacity, magnetic-only trip unit for motor protection and a 800A frame. Ideal for switchboard mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: NM8N-800S M 700A MCCB, Magnetic Motor Protection Circuit Breaker, 700A 3P MCCB, 50kA MCCB
- Product Type: Moulded case circuit breaker
- Rated Current: 700A
- Frame Size: 800A
- Number of Poles: 3P
- Release Type: Magnetic-only motor protection
- Breaking Capacity: 50kA
- Rated Frequency: 50/60Hz
- Rated Operational Voltage: Up to 690V AC
- Rated Insulation Voltage: Up to 1000V
- Installation: Fixed mounting with vertical or horizontal installation capability
- Connection: Front or rear connection options subject to selected configuration
- Mechanical Durability: Up to 6000 operating cycles
- Compliance Basis: IEC 60947-1 and IEC 60947-2
- Dimensions (H x L x W): 300mm x 210mm x 167mm
- Weight: 13 kg
- Magnetic-only trip unit designed for motor protection applications
- 700A rated current within an 800A frame
- 50kA short-circuit breaking capacity
- Three-pole configuration for three-phase systems
- Suitable for low-voltage distribution and motor feeder assemblies
- Magnetic trip setting range of approximately 6300–9800A
- Can be installed vertically or horizontally
- Suitable for use as a main or feeder protective device where coordinated overload protection is provided separately
- Installation, testing and commissioning must be carried out by a licensed electrician in accordance with the manufacturer's instructions, applicable Australian wiring rules and switchboard requirements. Magnetic-only protection does not provide thermal overload protection, so motor installations require correctly coordinated overload protection.
- Three-phase motor feeders
- Industrial switchboards
- Commercial low-voltage distribution boards
- Switchboard mains or feeder protection
- Motor control centres
- Industrial plant and machinery protection
- AS/NZS IEC 60947.2 for low-voltage circuit-breakers
- Long service life can reduce replacement frequency and associated material waste
- Metal and thermoplastic components may be recoverable through appropriate electrical equipment recycling streams
- Resettable circuit protection avoids routine replacement of fuses after fault operation
CHINT warranty policy provides 27 months from the date of manufacture for other low-voltage apparatus sold through authorised sales channels, subject to the applicable contract and warranty conditions.
Available through authorised CHINT distributors in Australia.