SCHNAP Logo

Making Trade Life Easy!
Trade Discount 25%

MCCB 3P 80A 50kA Magnetic Only 125A Frame NM8N Chint

BRAND: CABAC
SKU: 271848
$992.60 List price: $1,323.40
+ −
Chint NM8N 80A 3P MCCB features 50kA breaking capacity, magnetic-only trip unit for motor protection and a 125A frame. Ideal for switchboard mains protection.

Alternatively Known As: CHINT NM8N-125S M 80A 3P MCCB, Motor Protection MCCB, Magnetic Trip MCCB, Moulded Case Circuit Breaker

Technical Specifications
  • Product Type: Moulded Case Circuit Breaker (MCCB)
  • Series: NM8N-125S
  • Rated Current: 80A
  • Number of Poles: 3P
  • Frame Size: 125A
  • Trip Unit: Magnetic-only motor protection
  • Rated Voltage: Up to 690V AC
  • Rated Frequency: 50/60Hz
  • Breaking Capacity: 50kA
  • Installation: Fixed mounting with top or bottom line entry
  • Mounting Orientation: Vertical or horizontal
  • Mechanical Durability: Up to 15,000 operating cycles
  • Dimensions (H x L x W): 140mm x 78.5mm x 90mm
  • Weight: 1.24 kg
Key Features
  • Magnetic-only trip unit designed for motor protection applications
  • High 50kA short-circuit breaking capacity
  • 125A frame accommodates an 80A rated current
  • Three-pole configuration for three-phase circuits
  • Suitable for switchboard mains, feeder and motor circuit protection
  • Supports isolation and reliable low-voltage circuit switching
  • Optional auxiliary, alarm, shunt-trip and undervoltage accessories are available for the NM8N platform
Professional Installation Requirements
  • Installation, testing and commissioning must be carried out by a licensed electrician in accordance with AS/NZS 3000 and the manufacturer's instructions. Confirm coordination with the motor starter, overload relay and upstream protection before energising.
Applications
  • Three-phase motor circuit protection
  • Switchboard mains and feeder protection
  • Industrial power distribution
  • Commercial electrical switchboards
  • Short-circuit protection for motor control assemblies
Standards & Compliance
  • Applicable product standard: AS/NZS IEC 60947.2:2015 for low-voltage circuit-breakers
  • Installation should comply with AS/NZS 3000:2018 Wiring Rules
  • Australian RCM and EESS registration status should be verified for the specific supply channel before installation
Environmental Benefits
  • Durable moulded-case construction supports extended service life and reduces replacement waste
  • Copper and metal components are recyclable at end of service life
  • Magnetic motor protection can help limit damage to motors and associated equipment during short-circuit faults
  • Designed for repairable and accessory-supported switchboard assemblies, helping extend system service life
Warranty Information

CHINT's general policy for other low-voltage apparatus provides a 27-month warranty from the date of manufacture against defects in materials and workmanship when sold through authorised channels; contract terms may vary.

Available Now

Available through authorised CHINT distributors in Australia.