MCCB 3P 80A 70kA Thermal Magnetic 125A Frame NM8N Chint
Chint NM8N 80A 3P MCCB features 70kA breaking capacity, thermal-magnetic trip unit and a 125A frame. Ideal for switchboard mains and sub-mains protection.
Sign in
Please login to continue to your account.
Alternatively Known As: Moulded Case Circuit Breaker, MCCB, Thermal-Magnetic Circuit Breaker, 3P 80A 70kA MCCB
- Product Series: NM8N-125Q
- Rated Current: 80 A
- Number of Poles: 3P
- Frame Size: 125 A
- Trip Unit: Thermal-magnetic
- Ultimate Short-Circuit Breaking Capacity: 70 kA at AC 380/400/415 V
- Service Short-Circuit Breaking Capacity: 70 kA at AC 380/400/415 V
- Rated Insulation Voltage Ui: 1000 V
- Rated Impulse Withstand Voltage Uimp: 8 kV
- Rated Operational Voltage Ue: 380/400/415 V AC, 50/60 Hz
- Utilisation Category: Category A
- Connection: Fixed front connection
- Standard Product Reference: IEC/EN 60947-2
- Dimensions (H x L x W): 140mm x 78.5mm x 90mm
- Weight: 1.19 kg
- High 70kA short-circuit breaking capacity
- Thermal-magnetic overload and short-circuit protection
- Three-pole configuration for three-phase circuits
- 125A frame accommodates the 80A rated trip unit
- Suitable for switchboard mains and sub-mains protection
- Suitable for isolation
- Mechanical life of up to 25,000 operating cycles
- Electrical life of up to 10,000 operating cycles at AC 415V and rated current
- Installation, inspection and testing must be carried out by a licensed electrical contractor in accordance with AS/NZS 3000 and the switchboard manufacturer's requirements. Confirm prospective fault current, discrimination, cable capacity and terminal tightening before commissioning.
- Switchboard mains protection
- Sub-main protection
- Commercial and industrial distribution boards
- Three-phase power distribution systems
- Overload and short-circuit protection for feeders and equipment
- AS/NZS IEC 60947.2 is the applicable product standard for low-voltage circuit-breakers of this type
- AS/NZS 3000:2018 applies to selection, installation and verification within Australian electrical installations
- RoHS-declared product helps restrict the use of specified hazardous substances
- Durable construction and long operating life can reduce replacement frequency and associated waste
- Reusable metal and thermoplastic components support material recovery at end of service life
CHINT warranty policy covers other low-voltage apparatus against defects in materials and workmanship for 27 months from the date of manufacture when purchased through authorised sales channels; contract terms may vary.
Available through authorised CHINT distributors in Australia.